Plan Review Notes For Permit 04050039 |
Permit Number |
04050039 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-08 00:00:00 | ************ UNSAT **************** | | | | 1)NOTE: PLEASE SUBMIT PLANS/DRAWINGS | | TO SHOW ALL ELECTRICAL WORK IN SCOPE. | | PLANS MUST SHOW ALL ELECTRICAL TO MEET | | 2002 NEC MIN REQ'MENTS.215 | | | | 2)NOTE: PLEASE SEE FBC 104.2.1, PLANS | | BE BE A MIN OF 1/8 SCALE, BE CLEAR AND | | OF GOOD QUALITY. | | PLANS FOR THIS WORK MAY BE DRAWN BY | | OWNER, HOWEVER , PLANS MUST ALSO CONTAIN | | A PRINTED NAME AND SIGNATURE OF PERSON | | RESPONSIBLE FOR PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. PLEASE SUBMIT COMPLETE LAYOUT | | FOR ALL DEVICES/ LTS. PANEL SCHEDULE | | W/ ALL MIN CIRCUITS RISER DIAGRAM ETC. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|