Plan Review Notes
Plan Review Notes For Permit 04050039
Permit Number 04050039
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-08 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT PLANS/DRAWINGS
 TO SHOW ALL ELECTRICAL WORK IN SCOPE.
 PLANS MUST SHOW ALL ELECTRICAL TO MEET
 2002 NEC MIN REQ'MENTS.215
  
 2)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 BE BE A MIN OF 1/8 SCALE, BE CLEAR AND
 OF GOOD QUALITY.
 PLANS FOR THIS WORK MAY BE DRAWN BY
 OWNER, HOWEVER , PLANS MUST ALSO CONTAIN
 A PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE SUBMIT COMPLETE LAYOUT
 FOR ALL DEVICES/ LTS. PANEL SCHEDULE
 W/ ALL MIN CIRCUITS RISER DIAGRAM ETC.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]