2006-03-22 00:00:00 | *** DENIED *** | | 1) AHU'S 1&2 SUPPLY AIR DUCTS (30"X5") | | APPEARS TO SMALL FOR A 4 TON AND A 3 TON | | SYSTEM. PLEASE SUBMIT A MANUAL J FOR ALL | | UNITS SHOWING CFM'S AND DUCT SIZES, PER | | 2004 FBC/R M1401.3 . | | | | 2) AHU #4 SUPPLY AIR DUCT TO THE MASTER | | SUITE IS 14" AND THE RETURN AIR DUCT IS | | 12" TO ACHIEVE A BALANCE RETURN TI NEEDS | | TO BE 14" PLEASE CORRECT, PER 2004 FBC/R | | M1602.4 . | | | | 3) ELECTRIAL PLANS ARE SHOWING A GAS | | WATER HEATER ON THE SECOND FLOOR | | DRESSING ROOM CLOSET. PLEASE PROVIDE | | COMBUSTION AIR AND COMBUSTION AIR | | CALCULATIONS ON MECHANICAL PLANS, OR IF | | THERE IS NO WATER HEATER HAVE ELECT. | | PLANS CORRECTED. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|