Plan Review Notes
Plan Review Notes For Permit 04042064
Permit Number 04042064
Review Stop M
Sequence Number 5
Notes
Date Text
2006-03-22 00:00:00*** DENIED ***
 1) AHU'S 1&2 SUPPLY AIR DUCTS (30"X5")
 APPEARS TO SMALL FOR A 4 TON AND A 3 TON
 SYSTEM. PLEASE SUBMIT A MANUAL J FOR ALL
 UNITS SHOWING CFM'S AND DUCT SIZES, PER
 2004 FBC/R M1401.3 .
  
 2) AHU #4 SUPPLY AIR DUCT TO THE MASTER
 SUITE IS 14" AND THE RETURN AIR DUCT IS
 12" TO ACHIEVE A BALANCE RETURN TI NEEDS
 TO BE 14" PLEASE CORRECT, PER 2004 FBC/R
 M1602.4 .
  
 3) ELECTRIAL PLANS ARE SHOWING A GAS
 WATER HEATER ON THE SECOND FLOOR
 DRESSING ROOM CLOSET. PLEASE PROVIDE
 COMBUSTION AIR AND COMBUSTION AIR
 CALCULATIONS ON MECHANICAL PLANS, OR IF
 THERE IS NO WATER HEATER HAVE ELECT.
 PLANS CORRECTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  