 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 THESE ITEMS WERE REDLINED ON PREVIOUS
 PLANS AND NOT CORRECTED ON REVISIONS.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR IS
 NOT SUFFICIENT FOR THE SIZE OF THE
 SERVICE. THE SMALLEST ALLOWABLE FOR 400
 MCM FEEDERS IS #1/0CU PER 250.66. TWO
 CONDUCTORS CAN NOT BE SUBSTITUTED FOR
 THE SINGLE CONDUCTOR REQUIREMENT AS THEY
 CREATE PARALLEL GROUNDING PATHS.SEE
 250.6.
  
 2} SEE 250.50 FOR GROUNDING REQUIREMENTS
 INCLUDING FOOTER STEEL. LIST ALL
 AVAILABLE TO BE BONDED TOGETHER ON THE
 RISER DIAGRAM.
  
 3} THE RECEPTACLES ON THE PORTICO MUST
 BE GFI PER 210.8(A)(3). INDICATE SAME ON
 PLANS.
  
 THESE CORRECTIONS ARE DUE TO THE
 REVISION.
  
 1} SMOKE DETECTORS ARE REQUIRED AT THE
 STAIRS PER 905.2.2 FBC.
  
 2} SMOKE DETECTORS ARE REQUIRED INSIDE
 AND OUTSIDE BEDROOM #4 PER 8-1.4.1.6.2
 NFPA-72.
  
 3} THE VALUE OF THE PROJECT MUST BE
 INCREASED TO REFLECT ADDED SQUARE
 FOOTAGE. PLEASE NOTE SAME TO PERMIT
 SPECIALIST AT THE TIME OF RESUBMITTAL.
  
 PLEASE NOTE ALL KITCHEN COUNTERTOP
 RECEPTACLES MUST BE GFI PROTECTED PER
 210.8(A)(6). SEE COUNTERTOPS BETWEEN THE
 REFRIGERATOR'S.
  
 ALSO NOTE THE 250MCM CONDUCTORS FEEDING
 THE 200 AMP PANELS ARE OVERSIZED.
 ALTHOUGH NOT A VIOLATION IF THEY FIT
 UNDER THE LUGS, THEY MUST BE INSTALLED
 IF LEFT ON REVIEWED PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW