Date |
Text |
2005-02-25 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| |
| THESE ITEMS WERE REDLINED ON PREVIOUS |
| PLANS AND NOT CORRECTED ON REVISIONS. |
| |
| 1} THE GROUNDING ELECTRODE CONDUCTOR IS |
| NOT SUFFICIENT FOR THE SIZE OF THE |
| SERVICE. THE SMALLEST ALLOWABLE FOR 400 |
| MCM FEEDERS IS #1/0CU PER 250.66. TWO |
| CONDUCTORS CAN NOT BE SUBSTITUTED FOR |
| THE SINGLE CONDUCTOR REQUIREMENT AS THEY |
| CREATE PARALLEL GROUNDING PATHS.SEE |
| 250.6. |
| |
| 2} SEE 250.50 FOR GROUNDING REQUIREMENTS |
| INCLUDING FOOTER STEEL. LIST ALL |
| AVAILABLE TO BE BONDED TOGETHER ON THE |
| RISER DIAGRAM. |
| |
| 3} THE RECEPTACLES ON THE PORTICO MUST |
| BE GFI PER 210.8(A)(3). INDICATE SAME ON |
| PLANS. |
| |
| THESE CORRECTIONS ARE DUE TO THE |
| REVISION. |
| |
| 1} SMOKE DETECTORS ARE REQUIRED AT THE |
| STAIRS PER 905.2.2 FBC. |
| |
| 2} SMOKE DETECTORS ARE REQUIRED INSIDE |
| AND OUTSIDE BEDROOM #4 PER 8-1.4.1.6.2 |
| NFPA-72. |
| |
| 3} THE VALUE OF THE PROJECT MUST BE |
| INCREASED TO REFLECT ADDED SQUARE |
| FOOTAGE. PLEASE NOTE SAME TO PERMIT |
| SPECIALIST AT THE TIME OF RESUBMITTAL. |
| |
| PLEASE NOTE ALL KITCHEN COUNTERTOP |
| RECEPTACLES MUST BE GFI PROTECTED PER |
| 210.8(A)(6). SEE COUNTERTOPS BETWEEN THE |
| REFRIGERATOR'S. |
| |
| ALSO NOTE THE 250MCM CONDUCTORS FEEDING |
| THE 200 AMP PANELS ARE OVERSIZED. |
| ALTHOUGH NOT A VIOLATION IF THEY FIT |
| UNDER THE LUGS, THEY MUST BE INSTALLED |
| IF LEFT ON REVIEWED PLANS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |