Plan Review Notes
Plan Review Notes For Permit 04042064
Permit Number 04042064
Review Stop P
Sequence Number 3
Notes
Date Text
2004-09-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P2 THE SANITARY RISER DIAGRAM
 DOES NOT MEET CODE.
 A) CLEANOUTS ARE REQUIRED WHEN EVER THE
 BLDG DRAIN EXITS THE BLDG AND TIES INTO
 THE BLDG SEWER. 708.3.5
 B) WASH MACHINE REQUIRES A TRAP, STAND-
 PIPE AND CLEANOUT 4' ABOVE THE FLOOR.
 SECTIONS 1002.1, 802.4, & 708.10.
 C) INDICATE SIZE OF FLOOR DRAIN AND THE
 PIPING TO IT. SECTION 104.2.1
 D) MINIMUM SIZE TRAP FOR THE WASH MACH-
 INE IS 2" TABLE 709.1. RISER SHOWS 1-1/2
 INCH SANT. TO WASH MACHINE.
 E) LAV IN POWDER ROOM REQUIRES A VENT
 SECTION 901.2.1
 F) AIR ADMITENCE VALVES SHALL BE ABOVE
 THE TRAPS AT THE KITCHEN SINKS. SECTION
 917.4
 G) ALL TUBS, SHOWERS AND THE BIDET RE-
 QUIRE A TRAP. SECTION 1002.1
 H) CLEANOUT SHALL BE LOCATED BETWEEN
 THE FIRST AND SECOND FIXTURE BRANCHES
 OF THE BUILDING DRAIN ON THE RISER DIA-
 GRAM TO CORRELATE WITH THE FLAT DRAWING.
 SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]