2004-09-20 00:00:00 | CHECKLIST: |
| 1-PROVIDE COMPLETE ENGINEERING DESIGN |
| PACKAGE AND SPECS FOR PILE SYSTEM TO |
| BE USED AS REQUIRED BY SEC. 1805 FBC |
| 2001 AND AS NOTED ON SOIL TEST REPORT. |
| 2-PROVIDE DETAIL/SPECS SHOWING HOW ARE |
| STEEL COLUMNS ATTACHED TO I BEAMS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 3-PROVIDE DETAIL/SPECS SHOWING HOW ARE |
| WOOD TRUSSES ATTACHED TO I BEAM. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 4-PROVIDE UL LISTING AND COMPLETE SPECS |
| FOR FIREPLACE. SEC. 2806 FBC 2001. |
| 5-SHEET S8: A)SPECIFY HOW LONG NEED TO |
| BE THE WELDED STUDS. SEE UPPER LEFT |
| DETAILS. |
| B)SPECIFY HOW IS MASONRY WALL ATTACHED |
| TO I BEAM. HOW IS REINFORCING #5 BAR |
| WELDED TO I BEAM. |
| C)EXTERIOR EDGE CONDITION DETAIL IS |
| MISSING INFORMATION AT BOTTOM OF NOTE. |
| D)SPECIFY HOW IS MASONRY WALL ATTACHED |
| TO BEAM B-4. SEE DETAIL 8/S8.SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| E)PLANK ANCHORAGE DETAIL AT STEEL BEAM |
| DETAIL DOESN'T APPLY. PROVIDE ONLY |
| DETAILS THAT APPLY TO THIS PROJECT. |
| 6-OWES $641.36 FOR RE-SUBMITTAL FEES AND |
| UPDATING VALUE TO REFLECT A/C AREA |
| CHANGES. AND, ADDITIONAL RE-SUBMITTAL |
| FEES WILL BE REQUIRED. |
| 7-PROVIDE COMPLETE ELEVATOR INFORMATION |
| OR APPLY FOR SEPARATE PERMIT. |
| 8-NOTICE OF COMMENCEMENT NEEDS TO BE |
| RECORDED AND IS VOID AFTER 90 DAYS. |
| 9-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL |
| FOR STRUCTURAL CONNECTORS (SIMPSON OR |
| USP AS SPECIFIED ON PLANS). |
| 10-PROVIDE UPLIFT CALCULATIONS FOR HIP |
| GIRDER TRUSSES. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| B)TRUSSES WERE REVISED FROM METAL TO |
| WOOD. REVISE CONNECTOR FASTENERS AS |
| WELL. SEE SIMPSON LATEST CATALOGUE. |
| |