2004-07-12 00:00:00 | BUILDING REVIEWCOMMENTS: |
| 1-PROVIDE COMPLETE INFORMATION FOR THE |
| ELEVATOR OR APPLY FOR SEPARATE PERMIT. |
| 2-UPDATE NOTE #5 ON SHEET A1. SEE FBC |
| 2001 CHAPTER 13. |
| 3-CALCULATIONS FOR GARAGE BUCK DETAIL |
| NEED TO BE SIGNED, SEALED BY THE |
| ENGINEER/ARCHITECT. AND PROVIDE TITLE |
| BLOCK WITH ALL INFORMATION REQUIRED |
| BY CHAPTER 471/481 FLORIDA STATUTES. |
| 4-SHEET S-3 IS MISSING NOTE REGARDING |
| ROOF SHEATHING INSTALLATION. |
| 5-PROVIDE COMPLETE SPECIFICATIONS AND |
| DETAIL/SECTION AT THE ENDS OF I BEAM |
| SHOWING ATTACHMENT TO THE STRUCTURE. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 6-PROVIDE COMPLETE SPECIFICATIONS AND |
| DETAIL CONNECTIONS FOR 6" AND 8" H.C. |
| CONCRETE PLANK FLOOR SYSTEM. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC. |
| ARCHITECT TO REVIEW AND APPROVE |
| COMPLETE PAKCAGE PRIOR TO SUBMITTAL. |
| 7-PROVIDE DETAIL/SECTIONS AND SPECS FOR |
| RECESSED AREAS AT SHOWER AREAS IN H.C. |
| CONCRETE PLANKS. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 8-PROVIDE 2 COPIES OF COMPLETE FLORIDA |
| OR LOCAL PRODUCT APPROVAL FOR: |
| A)FRENCH DOOR WITH TRANSOM ABOVE SINGLE |
| ASSEMBLY AND PUT TOGETHER AS SHOWN ON |
| PLANS. SPECIFY ALL CONNECTIONS: DOOR |
| TO MULLION & FIXED WINDOW TO MULLION. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| B)STRUCTURAL CONNECTORS. |
| C)STRUCTURAL MULLIONS USED. |
| D)GARAGE DOOR. |
| E)ROOF TILE. |
| |
| 9-DETAIL FOR ARCHED OPENINGS DOESN'T |
| MATCH 2ND FLOOR STRUCTURAL PLAN. PLANS |
| CALL FOR BOND BEAMS, NOT POURED BEAMS. |
| ALSO, THERE ARE NO SPECS FOR SIZE AND |
| SPACING OF STIRRUPS. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 10-PROVIDE COMPLETE DETAIL SHOWING HOW |
| IS LINTEL L-1 REINFORCED WITH 2#5'S |
| AT BOTTOM OF PRECAST LINTEL?. IS IT A |
| SOLID OR "U" TYPE LINTEL?. SECTION |
| 104.2.1.2 CITY AMENDMENS TO FBC. |
| 11-NEED THE NOTICE OF COMMENCEMENT. |
| |