| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING |
| INSTALLED. MAINS/BRKRS AND PANELS ARE |
| ALL TO BE RATED FOR THE AVAILABLE FAULT |
| CURRENT. |
| PER 110.9/215.5 |
| |
| 2} THE GROUNDING ELECTRODE CONDUCTOR IS |
| UNDERSIZED PER 250.66. |
| |
| 3} THE GROUNDING ELECTRODE SYSTEM MUST |
| BE INSTALLED PER 250.50, ALL ITEMS |
| AVAILABLE MUST BE USED. PLEASE NOTE |
| SAME ON PLANS. |
| |
| 4} THE SERVICE CONDUCTORS @ 250 MCM ARE |
| UNDERSIZED FOR THE 400 AMP OCP MAIN. |
| SEE 310.15(B)(6).(400 MCM). |
| |
| 5} PLEASE LIST ALL THE REQUIRED |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE PER 210.11C3. |
| |
| 6} PLEASE LIST THE REQUIRED ARC |
| FAULT PROTECTED CIRCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 7} THE FOLLOWING APPLIANCE CIRCUITS |
| MUST BE CALCULATED AS INDICATED. |
| A) LAUNDRY PER 210.16(B)-1500VA. |
| B) DRYER PER 210.18-5000VA. |
| C) SMALL APPLIANCE 220.16(A)-1500 EA. |
| |
| 8} PLEASE PROVIDE A PANEL SCHEDULE SO |
| THAT CODE COMPLIANCE OF CIRCUITING CAN |
| BE DETERMINED. |
| |
| 9} A SMOKE DETECTOR MUST BE ADDED AT THE |
| STAIRWELL ON THE FIRST FLOOR TO COMPLY |
| WITH 905.2.2 F.B.C.. |
| |
| 10} THE ELEVATOR EQUIPMENT IS NOT LISTED |
| IN THE LOAD CALCULATION. |
| |
| 11} THE DISPOSAL IS NOT LISTED IN THE |
| CALCULATION. |
| |
| 12} THE GARAGE RECEPTACLES MUST COMPLY |
| WITH 210.8(A)(2). |
| |
| 13} THE RECEPTACLES ON THE PORTICO MUST |
| BE GFI PER 210.8(A)(3),GFI. |
| |
| 14} ALL OF THE OUTDOOR EQUIPMENT |
| DISCONNECTS MUST COMPLY WITH 110.26 |
| CLEARANCE. |
| |
| 15} THE PHONE NUMBER OF THE ARCHITECT |
| MUST BE CONTAINED IN THE TITLE BLOCK |
| PER 61G1-16.004(2) FAC. |
| |
| THE AREAS OF NON COMPLIANCE ARE NOTED ON |
| ONE SET OF REVIEWED PLANS TO AID THE |
| ARCHITECT IN MAKING CORRECTIONS. IF |
| THERE ARE ANY QUESTIONS PLEASE CALL. |
| |