Plan Review Notes
Plan Review Notes For Permit 04042064
Permit Number 04042064
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-02 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED TO PAY IMPACT FEES TO PALM BEACH
 COUNTY. BRING BACK DWGS WITH COUNTY
 STAMP AND PAID RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS TOO OLD. BESIDES,
 THIS FORM IS NOT REQUIRED. SEE SECTION
 1606.1.7 FBC 2001 FOR ALL 5 ITEMS TO
 BE INCLUDED IN DRAWINGS. REVISE SHEETS
 A1, S3 AND S7 TO INCLUDE ALL 5 ITEMS.
 4-NEED TO ADD THE ATTIC LIVE LOAD TO THE
 DESIGN CRITERIA AS REQUIRED BY TABLE
 1604.1 FBC 2001.
 5-PROVIDE 2 COPIES OF SOIL TEST REPORT
 WITH CORRECT ADDRESS & WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES WHEN
 SUBMITTING INFORMATION FOR PUBLIC
 RECORDS.
 6-REVISE HEIGHT OF PRIVACY WALL TO MEET
 ZONING STANDARDS. REMEMBER THAT SEPA-
 RATE PERMIT IS REQUIRED FOR THIS WALL.
 7-SHEET A1: A)NOTE #5. DESIGNER NEEDS TO
 SPECIFY CONNECTORS. DO NOT CITE AS PER
 CODE. SEC. 104.2.1 CITY AMENDMENTS TO
 FBC 2001.
 B)UPDATE NOTE #5: SEE CHAPTER 13 OF FBC
 2001 FOR CORRECT CODE SECTION.
 8-PROVIDE COMPLETE INFORMATION FOR
 ELEVATOR AS REQ'D BY SECTION 3001.1.1
 FBC 2001 OR PROVIDE ALL INFORMATION
 UNDER A SEPARATE PERMIT.
 9-SHEET A2: A)PROVIDE ATTIC ACCESS AT
 GARAGE AREA. SEC. 2309.6 FBC 2001.
 B)A FLIGHT OF STAIRS SHALL NOT HAVE A
 VERTICAL RISE OF MORE THAN 12FT BET.
 FLOORS OR LANDINGS. SEC. 1007.4.1 FBC.
 REVISE STAIRS AS REQUIRED.
 C)SPECIFY HOW IS THE 5/8" CEMENT BOARD
 ATTACHED TO 2X4'S. SPECIFY FASTENER &
 SPACING. SEC 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 D)PROVIDE SMOKE DETECTOR AT FIRST FLOOR
 BY THE STAIRWAY AS REQUIRED BY SECTION
 905.2.2 FBC 2001.
 10-SHEET A4: A)2ND FLOOR ROOF PROFILE
 DON'T MATCH 2ND FLOOR ROOF FRAMING
 PLAN ON SHEET S3. REVISE/CLARIFY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 11-SHEET A5:A)PROVIDE MANUFACTURER SPECS
 FOR CEMENT BOARD.
 B)ROOF SHEATHING NOTE: REVISE FASTENER
 FOR ROOF ZONE 3. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC.
 **ALSO, SEE FIGURE 1606.2(C) ON FBC 2001
 FOR LOCATION OF ZONE 3.
 C)SPECIFY SPECIFIC TILE STYLE USED TO
 PROPERLY CHECK PRODUCT APPROVAL.
 12-SHEET A7: A)PROVIDE SHOP DRAWINGS FOR
 BALCONIES GUARDRAILS.
 B)PROVIDE CALCS FOR GARAGE STRUCTURAL
 BUCK FASTENERS USED TO RESIST CALCULA-
 TED DESIGN PRESSURES. SEE PRODUCT
 APPROVAL FOR DOOR THAT MEET DESIGN
 PRESSURES CALCULATED AND CHECK RECO-
 MMENDATIONS FOR BUCK FASTENING. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)REVISE STAIR & ELEVATOR SECTION TO
 MATCH FOOTING SHOWN ON FOUNDATION PLAN
 AND SHOW ALL TIE BEAMS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 D)REVISE/CLARIFY SIZE OF ROOF TO MATCH
 SIZE SPECIFIED ON STRUCTURAL PLANS.
 13-ARCHITECT TO PROVIDE ALL INFORMATION
 AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTES WHEN SUBMITTING INFORMATION
 FOR PUBLIC RECORDS. SEE COPY OF SEC.
 61G1-16004 FOR TITLE BLOCK INFORMATION
 **ENGINEER TO PROVIDE ALL INFORMATION
 AS WELL AS REQUIRED BY CHAPTER 471 FL.
 STATUTES. SEE ATTACHED COPY OF SECTION
 61G15-23002 OF ADMINISTRATIVE CODE.
 EB #8613 IS NOT REGISTERED W/ FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
 14-SHEET S1: A)PROVIDE SECTION/DETAIL AT
 STEEL COLUMNS. SHOW TOP AND BOTTOM
 CONNECTORS AND EMBEDMENT OF CONCRETE
 PAD IN SOIL TO RESIST UPLIFT @ FRONT
 AND REAR PORCH COLUMNS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)CLARIFY FOOTING SCHEDULE: TABLE SAYS
 WF30 AND MEASURES 36". BUT FOUNDATION
 PLAN CALLS FOR WF36. REVISE AS REQ'D.
 C)SECTION DETAIL NUMBER AND SHEET KEYED
 ON PLANS TO MATCH NUMBER AND SHEET
 NUMBER SUBMITTED ON THIS SET.
 D)CLARIFY HOW ARE INTERIOR MASONRY WALLS
 REINFORCED. NOTE REGARDING #5 REINFOR-
 CEMENT APPLIES ONLY TO PERIMENTER
 WALLS. SEC. 104.2.1.2 CITY AMENDMENTS.
 15-SHEET S2:A)PROVIDE UPLIFT CALCS ON
 ROOF FRAMING PLAN. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)REVISE SPACING FOR ROOF SHEATHING
 FASTENER SPACING. SEE TABLE 2306.1 OF
 CITY AMENDMENTS TO FBC 2001 AND SEE
 FIGURE 1606.2(C) FBC 2001 FOR ZONE 3
 LOCATIONS.
 C)BEAM SCHEDULE: *BEAM B2 (ARCH BEAM)
 DOESN'T MATCH EXTERIOR ELEVATIONS.
 CLARIFY/REVISE AS REQUIRED.
 D)PROVIDE LINTEL SCHEDULE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **CLARIFY WHICH LINTELS ARE PRECAST AND
 WHICH ONES ARE PRESTRESED AS SPECIFIED
 ON NOTES AT BOTTOM OF BEAM SCHEDULE.
 E)CLARIFY HOW ARE TB-1 AND B1 INSTALLED
 BY THE DINING AREA IF THEY ARE AT
 DIFFERENT HEIGHTS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 F)WHAT ARE THE BOXES FOR SHOWN BY POWDER
 ROOM AND AT FAMILY BREAKFAST AREA?
 G)PROVIDE COMPLETE SPECS FOR I BEAM BY
 LAUNDRY AREA. SPECIFY CONNECTORS. ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 **PLAN CALLS FOR TB-1? REVISE AS REQ'D.
 H)SPECIFY/SHOW TIE BEAMS AT ELEVATOR
 SHAFT AREA. SEC 104.2.1.2 CITY AMENDM.
 I)CLARIFY HOW ARE H.C. PRECAST PLANKS
 SUPPORTED ON CONCRETE BLOCK WALLS IF
 INTERIOR WALLS ARE LOWER THAN BOTTOM
 OF PLANKS. SEC. 104.2.1.2 CITY AMENDM.
 J)PROVIDE COMPLETE SHOP DRAWINGS, SPECS
 FOR H.C. CONCRETE PLANK FLOOR SYSTEM.
 SHOW ALL CONNECTIONS, ETC. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 16-SHEET S3: A)PROVIDE UPLIFT CALCS AND
 TRUSS ANCHOR SCHEDULE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)ADD 30PSF OR 10PSF ATTIC LIVE LOAD AS
 REQUIRED BY TABLE 1604.1 FBC 2001.
 C)NOTE #5 CALLS FOR WIND LOAD TABLES ON
 SHEET S4. THERE ARE NONE. CLARIFY.
 D)MISSING ELEVATOR SHAFT. ALSO, SPECIFY
 TIE BEAM AT ELEVATOR SHAFT. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 E)ROOF LAYOUT DOESN'T MATCH EXTERIOR
 ELEVATIONS. REVISE AS REQUIRED.
 F)REVISE FASTENER TYPE & SPACING FOR
 SHEATHING AT END ZONES. SEE TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001 AND
 FIGURE 1606.2(C)FBC 2001.
 17-A)SHEET S4: A)REVISE TRUSS CONNECTOR.
 SEE 2004 SIMPSON CATALOGUE FOR REVISED
 CONNECTOR LOADS AS REQUIRED BY SECTION
 1609.4.3 FBC 2001. PROVIDE COMPLETE
 ENGINEERING CALCS AND ANALYSIS FOR
 NUMBER AND TYPE OF FASTENER USED THAT
 ARE DIFFERENT FROM THOSE PUBLISHED ON
 SIMPSON CATALOGUE.
 B)SECTION 2/S4: CLARIFY HOW ARE 2-1/2"
 TROUGH BOLTS INSTALLED ON 8"H.C. PLANK
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC
 C)CLARIFY IF BRACING OF MASONRY WALL W/
 STEEL ANGLE APPLIES TO BRACING OF ALL
 INTERIOR WALLS. SPECIFY ON PLANS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 D)SPECIFY ON SECTION THE REQUIRED EMBED-
 MENT OF FOOTING INTO THE SOIL. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001
 18-SHEET S5: A)REVISE TRUSS CONNECTOR
 FASTENER TYPE AND NUMBER TO BE USED TO
 MATCH 2004 SIMPSON CATALOGUE. SECTION
 1609.4.3 FBC 2001.
 B)SPECIFY DEPTH OF FOOTING IN RELATION
 TO THE FINISH GRADE. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 C)SECTION 4/S5:*SPECIFY SIZE OF I BEAM.
 **SPECIFY BRACING FOR GARAGE WALL.
 19-SHEET S6: A)SECTION 5/S6: *REVISE
 FOOTING TO MATCH FOOTING SHOWN ON FOUN
 DATION PLAN.
 **SHOW/SPECIFY ALL TIE BEAMS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)REVISE TRUSS CONNECTOR TO MATCH 2004
 SIMPSON CATALOGUE. SEC. 1606.9.4.3 FBC
 20-SHEET S7: A)PROVIDE ONLY THE DETAILS
 THAT APPLY TO THIS PROJECT AND MAKE
 SURE DETAILS PROVIDE ALL INFORMATION
 SUCH AS SIZES, ETC. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)REVISE TRUSS CONNECTOR. SEE COMMENTS
 ABOVE.
 21-PROVIDE COMPLETE DRAWINGS AND SPECS
 FOR CONCRETE STAIRS. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 22-PROVIDEPRODUCT APPROVAL FOR:
 A)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 B)ALL STRUCTURAL CONNECTORS.
 C)GARAGE DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED ON PLANS. NEED
 COMPLETE EVALUATION REPORT AND LEGIBLE
 DRAWINGS.
 D)CASEMENT WINDOWS. NEED WINDOWS THAT
 MEET THE DESIGN PRESSURES CALCULATED
 ON DRAWINGS.
 E)FIXED WINDOWS: NEED DADE COUNTY NOA
 REPORT AND DRAWINGS THAT MATCH NOA
 SPECIFIED ON FLORIDA PRODUCT APPROVAL
 COVER PAGE.
 F)MULLIONS: CLEARLY INDICATE ON DWGS
 SPECIFIC COMPONENTS TO BE USED:MULLION
 SIZE AND FASTENERS. ALSO, CHECK DESIGN
 PRESSURES SHOWN ON PLANS.
 G)ROOF TILE: NEED COMPLETE SBCCI REPORT
 AND DRAWINGS AND INDICATE SPECIFIC
 TILE STYLE AND FASTENING METHOD. CHECK
 PLANS FOR SPECIFICATIONS.
 23-ENERGY CALCULATIONS: A)MISSING INFO.
 FOR ADJACENT WALL.
 B)OWNER/AGENT TO SIGN AND DATE BOTTOM OF
 FORM.
 C)REVISE ORIENTATION OF OPENINGS TO
 MATCH ACTUAL HOUSE ORIENTATION.
 D)CLARIFY WHY THERE IS NOT OVERHANG
 LENGTH AND HEIGHT SPECIFIED.
 24-PROVIDE COMPLETE STRUCTURAL DETAILS
 FOR ARCHED OPENINGS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 25-PROVIDE COMPLETE STRUCTURAL DETAILS
 AND SPECS FOR SUSPENDED CEILING AT
 1ST FLOOR. SHOW HOW IS 5/8" DRYWALL
 SUPPORTED. SEC. 104.2.1.2 CITY AMENDM.
 26-OWES $1041.41 FOR UPDATED VALUATION
 AND RADON FEES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.