2004-06-02 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-NEED TO PAY IMPACT FEES TO PALM BEACH |
| COUNTY. BRING BACK DWGS WITH COUNTY |
| STAMP AND PAID RECEIPT. |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-DESIGN CERTIFICATION FOR BUILDING CODE |
| COMPLIANCE FORM IS TOO OLD. BESIDES, |
| THIS FORM IS NOT REQUIRED. SEE SECTION |
| 1606.1.7 FBC 2001 FOR ALL 5 ITEMS TO |
| BE INCLUDED IN DRAWINGS. REVISE SHEETS |
| A1, S3 AND S7 TO INCLUDE ALL 5 ITEMS. |
| 4-NEED TO ADD THE ATTIC LIVE LOAD TO THE |
| DESIGN CRITERIA AS REQUIRED BY TABLE |
| 1604.1 FBC 2001. |
| 5-PROVIDE 2 COPIES OF SOIL TEST REPORT |
| WITH CORRECT ADDRESS & WITH ENGINEER'S |
| ORIGINAL SEAL AND SIGNATURE AS REQ'D |
| BY CHAPTER 471 FLORIDA STATUTES WHEN |
| SUBMITTING INFORMATION FOR PUBLIC |
| RECORDS. |
| 6-REVISE HEIGHT OF PRIVACY WALL TO MEET |
| ZONING STANDARDS. REMEMBER THAT SEPA- |
| RATE PERMIT IS REQUIRED FOR THIS WALL. |
| 7-SHEET A1: A)NOTE #5. DESIGNER NEEDS TO |
| SPECIFY CONNECTORS. DO NOT CITE AS PER |
| CODE. SEC. 104.2.1 CITY AMENDMENTS TO |
| FBC 2001. |
| B)UPDATE NOTE #5: SEE CHAPTER 13 OF FBC |
| 2001 FOR CORRECT CODE SECTION. |
| 8-PROVIDE COMPLETE INFORMATION FOR |
| ELEVATOR AS REQ'D BY SECTION 3001.1.1 |
| FBC 2001 OR PROVIDE ALL INFORMATION |
| UNDER A SEPARATE PERMIT. |
| 9-SHEET A2: A)PROVIDE ATTIC ACCESS AT |
| GARAGE AREA. SEC. 2309.6 FBC 2001. |
| B)A FLIGHT OF STAIRS SHALL NOT HAVE A |
| VERTICAL RISE OF MORE THAN 12FT BET. |
| FLOORS OR LANDINGS. SEC. 1007.4.1 FBC. |
| REVISE STAIRS AS REQUIRED. |
| C)SPECIFY HOW IS THE 5/8" CEMENT BOARD |
| ATTACHED TO 2X4'S. SPECIFY FASTENER & |
| SPACING. SEC 104.2.1.2 CITY AMENDMENTS |
| TO FBC 2001. |
| D)PROVIDE SMOKE DETECTOR AT FIRST FLOOR |
| BY THE STAIRWAY AS REQUIRED BY SECTION |
| 905.2.2 FBC 2001. |
| 10-SHEET A4: A)2ND FLOOR ROOF PROFILE |
| DON'T MATCH 2ND FLOOR ROOF FRAMING |
| PLAN ON SHEET S3. REVISE/CLARIFY. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| 11-SHEET A5:A)PROVIDE MANUFACTURER SPECS |
| FOR CEMENT BOARD. |
| B)ROOF SHEATHING NOTE: REVISE FASTENER |
| FOR ROOF ZONE 3. SEE TABLE 2306.1 CITY |
| AMENDMENTS TO FBC. |
| **ALSO, SEE FIGURE 1606.2(C) ON FBC 2001 |
| FOR LOCATION OF ZONE 3. |
| C)SPECIFY SPECIFIC TILE STYLE USED TO |
| PROPERLY CHECK PRODUCT APPROVAL. |
| 12-SHEET A7: A)PROVIDE SHOP DRAWINGS FOR |
| BALCONIES GUARDRAILS. |
| B)PROVIDE CALCS FOR GARAGE STRUCTURAL |
| BUCK FASTENERS USED TO RESIST CALCULA- |
| TED DESIGN PRESSURES. SEE PRODUCT |
| APPROVAL FOR DOOR THAT MEET DESIGN |
| PRESSURES CALCULATED AND CHECK RECO- |
| MMENDATIONS FOR BUCK FASTENING. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| C)REVISE STAIR & ELEVATOR SECTION TO |
| MATCH FOOTING SHOWN ON FOUNDATION PLAN |
| AND SHOW ALL TIE BEAMS. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| D)REVISE/CLARIFY SIZE OF ROOF TO MATCH |
| SIZE SPECIFIED ON STRUCTURAL PLANS. |
| 13-ARCHITECT TO PROVIDE ALL INFORMATION |
| AS REQUIRED BY CHAPTER 481 FLORIDA |
| STATUTES WHEN SUBMITTING INFORMATION |
| FOR PUBLIC RECORDS. SEE COPY OF SEC. |
| 61G1-16004 FOR TITLE BLOCK INFORMATION |
| **ENGINEER TO PROVIDE ALL INFORMATION |
| AS WELL AS REQUIRED BY CHAPTER 471 FL. |
| STATUTES. SEE ATTACHED COPY OF SECTION |
| 61G15-23002 OF ADMINISTRATIVE CODE. |
| EB #8613 IS NOT REGISTERED W/ FLORIDA |
| BOARD OF PROFESSIONAL ENGINEERS. |
| 14-SHEET S1: A)PROVIDE SECTION/DETAIL AT |
| STEEL COLUMNS. SHOW TOP AND BOTTOM |
| CONNECTORS AND EMBEDMENT OF CONCRETE |
| PAD IN SOIL TO RESIST UPLIFT @ FRONT |
| AND REAR PORCH COLUMNS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)CLARIFY FOOTING SCHEDULE: TABLE SAYS |
| WF30 AND MEASURES 36". BUT FOUNDATION |
| PLAN CALLS FOR WF36. REVISE AS REQ'D. |
| C)SECTION DETAIL NUMBER AND SHEET KEYED |
| ON PLANS TO MATCH NUMBER AND SHEET |
| NUMBER SUBMITTED ON THIS SET. |
| D)CLARIFY HOW ARE INTERIOR MASONRY WALLS |
| REINFORCED. NOTE REGARDING #5 REINFOR- |
| CEMENT APPLIES ONLY TO PERIMENTER |
| WALLS. SEC. 104.2.1.2 CITY AMENDMENTS. |
| 15-SHEET S2:A)PROVIDE UPLIFT CALCS ON |
| ROOF FRAMING PLAN. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| B)REVISE SPACING FOR ROOF SHEATHING |
| FASTENER SPACING. SEE TABLE 2306.1 OF |
| CITY AMENDMENTS TO FBC 2001 AND SEE |
| FIGURE 1606.2(C) FBC 2001 FOR ZONE 3 |
| LOCATIONS. |
| C)BEAM SCHEDULE: *BEAM B2 (ARCH BEAM) |
| DOESN'T MATCH EXTERIOR ELEVATIONS. |
| CLARIFY/REVISE AS REQUIRED. |
| D)PROVIDE LINTEL SCHEDULE. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| **CLARIFY WHICH LINTELS ARE PRECAST AND |
| WHICH ONES ARE PRESTRESED AS SPECIFIED |
| ON NOTES AT BOTTOM OF BEAM SCHEDULE. |
| E)CLARIFY HOW ARE TB-1 AND B1 INSTALLED |
| BY THE DINING AREA IF THEY ARE AT |
| DIFFERENT HEIGHTS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| F)WHAT ARE THE BOXES FOR SHOWN BY POWDER |
| ROOM AND AT FAMILY BREAKFAST AREA? |
| G)PROVIDE COMPLETE SPECS FOR I BEAM BY |
| LAUNDRY AREA. SPECIFY CONNECTORS. ETC. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| **PLAN CALLS FOR TB-1? REVISE AS REQ'D. |
| H)SPECIFY/SHOW TIE BEAMS AT ELEVATOR |
| SHAFT AREA. SEC 104.2.1.2 CITY AMENDM. |
| I)CLARIFY HOW ARE H.C. PRECAST PLANKS |
| SUPPORTED ON CONCRETE BLOCK WALLS IF |
| INTERIOR WALLS ARE LOWER THAN BOTTOM |
| OF PLANKS. SEC. 104.2.1.2 CITY AMENDM. |
| J)PROVIDE COMPLETE SHOP DRAWINGS, SPECS |
| FOR H.C. CONCRETE PLANK FLOOR SYSTEM. |
| SHOW ALL CONNECTIONS, ETC. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 16-SHEET S3: A)PROVIDE UPLIFT CALCS AND |
| TRUSS ANCHOR SCHEDULE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| B)ADD 30PSF OR 10PSF ATTIC LIVE LOAD AS |
| REQUIRED BY TABLE 1604.1 FBC 2001. |
| C)NOTE #5 CALLS FOR WIND LOAD TABLES ON |
| SHEET S4. THERE ARE NONE. CLARIFY. |
| D)MISSING ELEVATOR SHAFT. ALSO, SPECIFY |
| TIE BEAM AT ELEVATOR SHAFT. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| E)ROOF LAYOUT DOESN'T MATCH EXTERIOR |
| ELEVATIONS. REVISE AS REQUIRED. |
| F)REVISE FASTENER TYPE & SPACING FOR |
| SHEATHING AT END ZONES. SEE TABLE |
| 2306.1 CITY AMENDMENTS TO FBC 2001 AND |
| FIGURE 1606.2(C)FBC 2001. |
| 17-A)SHEET S4: A)REVISE TRUSS CONNECTOR. |
| SEE 2004 SIMPSON CATALOGUE FOR REVISED |
| CONNECTOR LOADS AS REQUIRED BY SECTION |
| 1609.4.3 FBC 2001. PROVIDE COMPLETE |
| ENGINEERING CALCS AND ANALYSIS FOR |
| NUMBER AND TYPE OF FASTENER USED THAT |
| ARE DIFFERENT FROM THOSE PUBLISHED ON |
| SIMPSON CATALOGUE. |
| B)SECTION 2/S4: CLARIFY HOW ARE 2-1/2" |
| TROUGH BOLTS INSTALLED ON 8"H.C. PLANK |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| C)CLARIFY IF BRACING OF MASONRY WALL W/ |
| STEEL ANGLE APPLIES TO BRACING OF ALL |
| INTERIOR WALLS. SPECIFY ON PLANS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| D)SPECIFY ON SECTION THE REQUIRED EMBED- |
| MENT OF FOOTING INTO THE SOIL. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001 |
| 18-SHEET S5: A)REVISE TRUSS CONNECTOR |
| FASTENER TYPE AND NUMBER TO BE USED TO |
| MATCH 2004 SIMPSON CATALOGUE. SECTION |
| 1609.4.3 FBC 2001. |
| B)SPECIFY DEPTH OF FOOTING IN RELATION |
| TO THE FINISH GRADE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| C)SECTION 4/S5:*SPECIFY SIZE OF I BEAM. |
| **SPECIFY BRACING FOR GARAGE WALL. |
| 19-SHEET S6: A)SECTION 5/S6: *REVISE |
| FOOTING TO MATCH FOOTING SHOWN ON FOUN |
| DATION PLAN. |
| **SHOW/SPECIFY ALL TIE BEAMS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)REVISE TRUSS CONNECTOR TO MATCH 2004 |
| SIMPSON CATALOGUE. SEC. 1606.9.4.3 FBC |
| 20-SHEET S7: A)PROVIDE ONLY THE DETAILS |
| THAT APPLY TO THIS PROJECT AND MAKE |
| SURE DETAILS PROVIDE ALL INFORMATION |
| SUCH AS SIZES, ETC. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| B)REVISE TRUSS CONNECTOR. SEE COMMENTS |
| ABOVE. |
| 21-PROVIDE COMPLETE DRAWINGS AND SPECS |
| FOR CONCRETE STAIRS. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 22-PROVIDEPRODUCT APPROVAL FOR: |
| A)FRENCH DOORS WITH TRANSOM ABOVE SINGLE |
| ASSEMBLY AS SHOWN ON PLANS. |
| B)ALL STRUCTURAL CONNECTORS. |
| C)GARAGE DOORS THAT MEET THE DESIGN |
| PRESSURES CALCULATED ON PLANS. NEED |
| COMPLETE EVALUATION REPORT AND LEGIBLE |
| DRAWINGS. |
| D)CASEMENT WINDOWS. NEED WINDOWS THAT |
| MEET THE DESIGN PRESSURES CALCULATED |
| ON DRAWINGS. |
| E)FIXED WINDOWS: NEED DADE COUNTY NOA |
| REPORT AND DRAWINGS THAT MATCH NOA |
| SPECIFIED ON FLORIDA PRODUCT APPROVAL |
| COVER PAGE. |
| F)MULLIONS: CLEARLY INDICATE ON DWGS |
| SPECIFIC COMPONENTS TO BE USED:MULLION |
| SIZE AND FASTENERS. ALSO, CHECK DESIGN |
| PRESSURES SHOWN ON PLANS. |
| G)ROOF TILE: NEED COMPLETE SBCCI REPORT |
| AND DRAWINGS AND INDICATE SPECIFIC |
| TILE STYLE AND FASTENING METHOD. CHECK |
| PLANS FOR SPECIFICATIONS. |
| 23-ENERGY CALCULATIONS: A)MISSING INFO. |
| FOR ADJACENT WALL. |
| B)OWNER/AGENT TO SIGN AND DATE BOTTOM OF |
| FORM. |
| C)REVISE ORIENTATION OF OPENINGS TO |
| MATCH ACTUAL HOUSE ORIENTATION. |
| D)CLARIFY WHY THERE IS NOT OVERHANG |
| LENGTH AND HEIGHT SPECIFIED. |
| 24-PROVIDE COMPLETE STRUCTURAL DETAILS |
| FOR ARCHED OPENINGS. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 25-PROVIDE COMPLETE STRUCTURAL DETAILS |
| AND SPECS FOR SUSPENDED CEILING AT |
| 1ST FLOOR. SHOW HOW IS 5/8" DRYWALL |
| SUPPORTED. SEC. 104.2.1.2 CITY AMENDM. |
| 26-OWES $1041.41 FOR UPDATED VALUATION |
| AND RADON FEES. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |