Plan Review Notes
Plan Review Notes For Permit 04042035
Permit Number 04042035
Review Stop P
Sequence Number 2
Notes
Date Text
2004-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: SHT A-1 DETAIL
 #3 SHOW COMPLIANCE FOR SECTION 11-4.24.6
 EXPOSED PIPES AND SURFACES ON PLANS.
 2) FROM PREVIOUS REVIEW: SHT PO.1 DOMES-
 TIC WATER ISOMETRIC, THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIX-
 TURE NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS
 3) CORRECT THE CERTIFICATE OF AUTHORIZ-
 ATION NUMBER REQUIRED BY 61G15-23.002(2)
 AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]