Plan Review Notes For Permit 04042035 |
Permit Number |
04042035 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-30 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2) IN THE DOOR SCHEDULE REMARKS NONE | | ARE MADE FOR DOOR 611. ANY REASON FOR | | THIS DOOR NOT TO BE FIRE RATED. | | | | 3) IT APPEARS THAT DOOR 625 DOES NOT | | NEED TO BE FIRE RATED. THE DOOR | | SCHEDULE INDICATES THAT IT IS. PLEASE | | EXPLAIN. | | | | 4) KEY NOTES ON PAGE A-1 INDICATES | | # 8, CARD READER FOR ENTRY AND EXIT | | PLEASE EXPLAIN FURTHER. | | | | 5) SEPARATE PLANS AND PERMITS | | REQUIRED FOR FIRE SPRINKLER SYSTEM | | REMODEL. | | | | 6) SEPARATE PLANS AND PERMITS | | REQUIRED FOR FIRE ALARM SYSTEM | | REMODEL. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|