2004-05-04 00:00:00**********UNSAT *****************
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD
 -S AT 125%(LIGHTING ETC)(LARGEST MOTORS)
 215.2,215.3,230.42,210.19A,210.20A ETC
  
 2)NOTE: PLEASE 250.30 FOR GROUNDING
 OF TRANSFORMER. PLEASE SHOW ATTACHMENT(S
  
 3)NOTE: PLEASE CLARIFY ELECTRICAL ROOM
 SHOWS ELEVATED BUS DUCT WITH DISC AT THE
 SAME LOCATION. PLEASE SEE RISER DIAGRAM,
 INDICATES DISCONNECT UNDER METER?
 PLEASE CORRELATE PLANS/W/ RISER
  
 4)NOTE: PLEASE VERIFY 1/0 CONDUCTORS
 SHOWN FOR 70A FEED TO TRANSFORMER.
 1/0'S ARE PERMITTED, HOWEVER, PLEASE
 VERIFY IF THIS SIZE CONDUCTOR WILL FIT
 INTO 70A BRKR? THIS IS A CLARIFICATION
 NOTE ONLY..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  