2004-05-24 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| AND A COPY SUBMITTED TO THIS OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2) FBC 704.3.1 & 1004.1.4(2)SHEET A-1, |
| FLOOR PLAN.THE NEW SECTIONS OF TENANT |
| WALL AT CORRIDOR NORTH AND CORRIDOR |
| EAST SHALL BE ONE-HOUR FIRE-RATED. |
| AMEND THE PLAN. |
| |
| 3) FBC 704.3.1 & 1004.1.4(2)SHEET A-2, |
| DETAIL 6.WHAT IS THE U.L. LISTING |
| REFERENCE FOR THE HORIZONTAL SHAFT WALL? |
| ANNOTATE THE PLANS. |
| |
| 4) FBC TABLE 705.1.2SHEET A-1, DOOR |
| SCHEDULE.DOOR 611 SHALL HAVE A FIRE |
| RESISTANCE RATING OF 20MINUTES.AMEND |
| THE SCHEDULE. |
| |
| 5) FBC 11-4.24SHEET A-1, LOUNGE SINK |
| DEPTH AND KNEE CLEARANCE.IT IS NOTED |
| THAT DETAIL 3 SHOWS 'NO BASE' FOR THE |
| UNDER-SINK CABINET.THE SINK SHALL BE A |
| MAXIMUM OF 6-1/2" DEEP AND THE KNEE |
| CLEARANCE UNDER THE SINK SHALL BE AT |
| LEAST 27" HIGH, 30" WIDE AND 19" DEEP. |
| ANNOTATE THE PLANS TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 6) FBC 2405.2SHEET A-1. THE GLAZING |
| SHOWN IN THE ELEVATIONAL VIEW OF DOOR |
| TYPE C IS NOT REFERENCED IN THE DOOR |
| SCHEDULE, FOR DOOR #603.THE GLAZING |
| IS IN A 'HAZARDOUS LOCATION' AND IS |
| REQUIRED TO BE SAFETY GLASS SATISFYING |
| THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| SAFETY COMMISSION 16, CODE OF FEDERAL |
| REGULATIONS, PART 1201 (CPSC 16-CFR, |
| PART 1201).SUBMIT DETAILS TO |
| DEMONSTRATE COMPLIANCE. |
| |
| 7) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |