2007-01-11 09:15:24PROVISO:
  
 1.PLEASE CLARIFY THE FOLLOWING; PLAN SHEET M2.1A NOTE
 INDICATES THE CO SENSORS ARE TO MOUNTED AT 96" AFF.
 PLEASE PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 FOR THE CO SENSORS.PLEASE NOTE, GARAGE VENTILATION IS
 DEPENDANT ON CO SENSORS ACTIVIATION, PLEASE CLARIFY HOW
 THIS WILL BE CODE COMPLIANT SHOULD THE BUILDING HAVE
 LOSS OF POWER.
  
 2. PLAN SHEET M2.1,VENTILATION TO THE MECHANICAL
 ROOM, PER 2001 FMC 401.5.1, MECHANICAL INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10FTFROM ANY HAZARDOUS
 OR NOXIOUS CONTAMINANT SUCH AS PARKING LOTS.
  
 3.PLEASE NOTE, RESPONSE OR REVISIONS GENERATED BY
 COMMENT 2 BY BUILDING PLANS EXAMINER, JIM WITMER MAY
 IMPACT THE NEED FOR DAMPERS AT RATED PARTITIONS.
  