Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop FIRE
Sequence Number 9
Notes
Date Text
2007-01-16 10:22:01***DENIED***
  
 1) FIRE EXTINGUISHERS ARE SHOWN ON SOME SHEETS, BUT
 MISSING ON OTHERS. WHEN THE LOCATIONS ARE ILLUSTRATED,
 PLACEMENT SHALL BE WITHIN 75' TRAVEL DISTANCE.
  
 2) NEW FIRE DAMPER INSTALLATIONS SHALL BE TESTED FOR
 CLOSURE PRIOR TO FINAL INSPECTION.
  
 3) IF SEPARATE SHOP DRAWINGS AND PERMIT HAS BEEN ISSUED
 FOR FIRE ALARM SYSTEM, CHANGES TO THAT SYSTEM TO BE
 SUBMITTED UNDER THAT PERMIT.
  
 4) SOME SMOKE DETECTORS APPEAR TO BE MISSING FROM
 ELEVATOR LOBBIES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW