2007-01-17 10:44:37REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT P2.1A. THERE ARE MANY CHANGES NOT INDICATED AS
 REVISIONS. NO CLOUDS ARE INDICATED ON THE SHEET FOR
 THESE REVISIONS. REVISIONS 13, 19, & 20 ARE NOT SHOWN
 ON THE PLANS BUT ARE SHOWN ON THE REVISION LIST. PLEASE
 CLARIFY, AS THE LATEST APPROVED REVISION PRIOR TO THIS
 SUBMITTAL IS REVISION #5.
  
 2. SHT P2.1B. THERE ARE REVISIONS FOUND THAT WERE NOT
 CLOUDED NOR INDICATED AS REVISIONS. REVISION #14 WAS
 NOT FOUND. THE LATEST REVISION PRIOR TO THIS SUBMITTAL
 IS REVISION #12. PLEASE CLARIFY.
  
 3. SHT P5.1. THERE ARE MANY REVISIONS NOT CLOUDED NOR
 INDICATED AS REVISIONS. REVISIONS 13, 19 & 20 ON THE
 REVISION LIST WERE NOT FOUND ON THE PLANS. THE LAST
 APPROVED REVISION PRIOR TO THIS SUBMITTAL IS #5. PLEASE
 CLARIFY.-THE MOP SINK MOVED TO THE NEW LOCATION IN
 NOT VENTED. SECTION 901.2.1.
  
 4. SHT P6.1. THERE ARE REVISIONS NOT CLOUDED NOR
 INDICATED AS REVISIONS. SOME REVISIONS HAVE NOT BEEN
 FOUND ON THE PLANS. PLEASE CLARIFY.-THE WATER
 HAMMER ARRESTORS FOR THE MOP SINK IN THE NEW LOCATION
 AND FOR THE LAV NEAR THE CAFE SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  