2006-09-06 00:00:00PROVISO:
 THE FOLLOWING SHEETS NEED TO BE REVISED,
 DELETING THE HEAT EXCHANGER AND PUMPS 3
 & 4:M0.1, M2.6, M7.1, & M8.1.
  
 PLEASE NOTE:
 VARIANCE APPROVED NOVEMBER 18, 2004 WITH
 THE FOLLOWING CONDITIONS TO BE SET
 FORTH:
 1) OFFICE OPENINGS REDUCED TO 25.5% &
 EXPAND THE SPRINKLER SYSTEM TO
 INCLUDE SPRINKLER HEADS ON BOTH
 SIDES OF THE GLASS FILLED OPENINGS.
 2) GARAGE OPENINGS REDUCED TO 20% &
 EXPAND FIRE SPRINKLER SYSTEM TO
 HAVESPRINKLER HEAD OVER ALL
 OPENINGS
 3) ELEVATIONS HAVE BEEN CHANGED TO
 AESTHETICALLY IMPROVE THE
 APPEARANCE OF THE GARAGE BUILDING.
  
 PLEASE NOTE, THIS SHOULD ALSO INCLUDE
 ALL MECHANICAL OPENINGS, LOUVERS FOR
 EXHAUST & AIR INTAKES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.