Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop P
Sequence Number 4
Notes
Date Text
2005-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - THIS HAS BEEN POINTED OUT
 TO THE ENGINEER IN THE PAST AND IS STILL
 REQUIRED.
  
 2) SHTS P3.1A AND P61. THE WATER RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN
 AT COL. LINES B/X1 THRU A/X1. ALSO THE
 HOSE BIBB AT COL. LINE C/X3 IS NOT SHOWN
 ON THE RISER DIAGRAM. THIS COULD HAVE
 BEEN A PROVISO BUT SINCE THE PLANS WERE
 DENIED BY COMMENT #1 THIS CAN BE
 ADDRESSED AT THIS TIME.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]