2005-05-26 00:00:00DENIED:
 1.PLAN INDICATES THE FIRST FLOOR LOBBY
 AREA OPEN TO THE SECOND FLOOR LOBBY AND
 EGRESS CORRIDOR.SHOW COMPLIANCE WITH
 2001 FBC 414 & 2001 FBC/ M 403.6.6.
 PROVIDE TOTAL CUBIC FEET CALCULATION FOR
 THE AREA IN QUESTION.
  
 PROVISO:
 VARIANCE APPROVED NOVEMBER 18, 2005 WITH
 THE FOLLOWING CONDITIONS TO BE SET
 FORTH:
 1) OFFICE OPENINGS REDUCED TO 25.5% &
 EXPAND THE FIRE SPRINKLER SYSTEM TO
 INCLUDE SPRINKLER HEADS ON BOTH
 SIDES OF THE GLASS FILLED OPENINGS
 2) GARAGE OPENINGS REDUCED TO 20% &
 EXPAND FIRE SPRINKLER SYSTEM TO HAVE
 SPRINKLER HEAD OVER ALL OPENINGS
 3) ELEVATIONS HAVE BEEN CHANGED TO
 AESTHETICALLY IMPROVE THE APPEARANCE
 OF THE GARAGE BUILDING.
  
 PLEASE NOTE, THIS SHOULD ALSO INCLUDE
 ALL MECHANICAL OPENINGS, LOUVERS FOR
 EXHAUST & AIR INTAKES.
  