2005-03-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| A) FROM PREVIOUS REVIEW: COMMENT NUMBERS |
| SHALL STAY THE SAME TO AVOID CONFUSION. |
| 1) A TITLE BLOCK MUST APPEAR ON ALL |
| ARCHITECTURAL DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK |
| MUST, AT A MINIMUM, CONTAIN THE |
| FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| NUMBER. |
| IF THE FIRM NAME IS A CORP., PARTNERSHIP |
| OR A FICITIOUS NAME A CERTIFICATE OF |
| AUTHORIZATION IS REQUIRED. 61G1-16.004 & |
| FS 481.219 FS 481.2055 - NO RESPONSE |
| NOTED. |
| 3) DRINKING FOUNTAINS ARE REQUIRED PER |
| TABLE 403.1. RESPONSE NOTED, BUT IF THIS |
| IS A NEW BUILDING THEN HOW CAN THERE BE |
| EXISTING DRINKING FOUNTAINS? NO DRINKING |
| FOUNTAINS ARE SHOWN ON THE FLOOR PLAN OR |
| THE SANT. RISER DIAGRAM. |
| 4) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| COMPLIANCE FOR GREASE INTERCEPTOR. WASTE |
| ORD #2938-96. (561) 837-4074. RESPONSE |
| NOTED, BUT THIS IS NOT A PERMIT ISSUE. |
| THIS IS TO SEE IF A GREASE INTERCEPTOR |
| WILL BE REQUIRED, AND IF ONE IS A GREASE |
| LINE CAN BE BROUGHT INTO THE BUILDING |
| NOW RATHER THAN TEARING UP THE FLOOR IN |
| THE FUTURE. |
| *********NEW COMMENTS SOME BECAUSE OF |
| CHANGES IN THE PLANS OR NEW SHEETS****** |
| 1B) SHT P2.1 LABELED AS SANITARY, BUT |
| HAS STORM AND CONDENSATE ALSO. - STORM |
| LINE AT COL. LINE B?X9 DOES NOT REFLECT |
| THE RISER ON SHT P7.1. RISER DIAGRAM |
| SHOWS 2 STORM RISERS, BUT FLOOR PLAN |
| SHOWS ONLY ONE. PLEASE CORRELATE FLOOR |
| PLAN AND RISER DIAGRAM. |
| 2B) SHTS P2.1A & P5.1 FLOOR DRAIN IN |
| PUMP NOT VENTED. SECTION 901.2.1. |
| 3B) SHTS P2.1A & P5.1 PIPING UPSTREAM OF |
| THE PUMP ROOM FLOOR DRAINS, THE FLOOR |
| PLAN AND RISER DIAGRAM DO NOT REFLECT |
| EACH OTHER. FLOOR PLAN SHOWS 6" PIPING |
| AND THE RISER DIAGRAM SHOWS 8" PLEASE |
| CORRELATE. SECTION 104.2.1. |
| 4B) SHTS P2.1A & P5.1 SANT. RISER |
| DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| THE COFFEE SHOP IN NOT ON THE RISER |
| DIAGRAM. PLEASE CORRELATE. SECTION |
| 104.2.1. |
| 5B) SHTS P2.1B & P5.1 SANT. RISER |
| DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| SANT. RISER DIAGRAM SHOWS 4" TO THE |
| TICKED BOOTH AND THE FLOOR PLAN SHOWS |
| 6". PLEASE CLARIFY. SECTION 104.2.1. |
| 6B) SHTS P2.2B, P2.3B SHOW STORM DRAINS |
| AS FLOOR DRAINS ON THE FLOOR PLAN, BUT |
| ARE SHOWN AS DECK DRAINS ON THE STORM |
| RISER SHT P7.1. PLEASE CORRELATE/CLARIFY |
| SECTION 104.2.1. |
| 7B) SHTS P2.2B, P2.3B, P2.4B & P2.5B ARE |
| LABELED AS SANITARY FLOOR PLANS, BUT THE |
| INFORMATION IS FOR STORM DRAINAGE. |
| PLEASE CLARIFY. SECTION 104.2.1. |
| 8B) SHTS P2.5B & P7.1 DO NOT REFLECT |
| EACH OTHER. STORM RISER DIAGRAM DOES NOT |
| SHOW 2" PLANTER DRAIN LINE. PLEASE |
| CORRELATE SHEETS. SECTION 104.2.1. |
| 9B) SHT P5.1 STACKS FOR LAVS NOT SIZED |
| CORRECTLY. MAXIMUM 10 DFU'S ON 2" STACK |
| WITH 3 BRANCH INTERVALS OR LESS. 18 DFU |
| SHOWN. TABLE 710.1(2). |
| 10B) SHTS P3.19 & P6.1 FULL OPEN VALVES |
| REQUIRED ON THE WATER DISTRIBUTION |
| SUPPLY PIPE AT THE ENTRANCE INTO THE |
| STRUCTURE, SECTION 606.1(2), AND ON THE |
| TOP OF EVERY WATER DOWN-FEED PIPE, |
| SECTION 606.1(4). |
| 11B) SHT P6.1 WATER LINE TO TICKET BOOTH |
| NOT SHOWN ON THE WATER RISER DIAGRAM. - |
| WATER LINE BY COL. X7 NOT SHOWN ON THE |
| WATER RISER DIAGRAM. -DOES NOT REFLECT |
| THE WATER PIPING SHOWN ON SHT P3.1A BY |
| COL. LINES B/X1!!! THRU A"/X1. |
| |