Date Text
2005-03-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEW: COMMENT NUMBERS
 SHALL STAY THE SAME TO AVOID CONFUSION.
 1) A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 IF THE FIRM NAME IS A CORP., PARTNERSHIP
 OR A FICITIOUS NAME A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED. 61G1-16.004 &
 FS 481.219 FS 481.2055 - NO RESPONSE
 NOTED.
 3) DRINKING FOUNTAINS ARE REQUIRED PER
 TABLE 403.1. RESPONSE NOTED, BUT IF THIS
 IS A NEW BUILDING THEN HOW CAN THERE BE
 EXISTING DRINKING FOUNTAINS? NO DRINKING
 FOUNTAINS ARE SHOWN ON THE FLOOR PLAN OR
 THE SANT. RISER DIAGRAM.
 4) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR GREASE INTERCEPTOR. WASTE
 ORD #2938-96. (561) 837-4074. RESPONSE
 NOTED, BUT THIS IS NOT A PERMIT ISSUE.
 THIS IS TO SEE IF A GREASE INTERCEPTOR
 WILL BE REQUIRED, AND IF ONE IS A GREASE
 LINE CAN BE BROUGHT INTO THE BUILDING
 NOW RATHER THAN TEARING UP THE FLOOR IN
 THE FUTURE.
 *********NEW COMMENTS SOME BECAUSE OF
 CHANGES IN THE PLANS OR NEW SHEETS******
 1B) SHT P2.1 LABELED AS SANITARY, BUT
 HAS STORM AND CONDENSATE ALSO. - STORM
 LINE AT COL. LINE B?X9 DOES NOT REFLECT
 THE RISER ON SHT P7.1. RISER DIAGRAM
 SHOWS 2 STORM RISERS, BUT FLOOR PLAN
 SHOWS ONLY ONE. PLEASE CORRELATE FLOOR
 PLAN AND RISER DIAGRAM.
 2B) SHTS P2.1A & P5.1 FLOOR DRAIN IN
 PUMP NOT VENTED. SECTION 901.2.1.
 3B) SHTS P2.1A & P5.1 PIPING UPSTREAM OF
 THE PUMP ROOM FLOOR DRAINS, THE FLOOR
 PLAN AND RISER DIAGRAM DO NOT REFLECT
 EACH OTHER. FLOOR PLAN SHOWS 6" PIPING
 AND THE RISER DIAGRAM SHOWS 8" PLEASE
 CORRELATE. SECTION 104.2.1.
 4B) SHTS P2.1A & P5.1 SANT. RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE COFFEE SHOP IN NOT ON THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
 5B) SHTS P2.1B & P5.1 SANT. RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 SANT. RISER DIAGRAM SHOWS 4" TO THE
 TICKED BOOTH AND THE FLOOR PLAN SHOWS
 6". PLEASE CLARIFY. SECTION 104.2.1.
 6B) SHTS P2.2B, P2.3B SHOW STORM DRAINS
 AS FLOOR DRAINS ON THE FLOOR PLAN, BUT
 ARE SHOWN AS DECK DRAINS ON THE STORM
 RISER SHT P7.1. PLEASE CORRELATE/CLARIFY
 SECTION 104.2.1.
 7B) SHTS P2.2B, P2.3B, P2.4B & P2.5B ARE
 LABELED AS SANITARY FLOOR PLANS, BUT THE
 INFORMATION IS FOR STORM DRAINAGE.
 PLEASE CLARIFY. SECTION 104.2.1.
 8B) SHTS P2.5B & P7.1 DO NOT REFLECT
 EACH OTHER. STORM RISER DIAGRAM DOES NOT
 SHOW 2" PLANTER DRAIN LINE. PLEASE
 CORRELATE SHEETS. SECTION 104.2.1.
 9B) SHT P5.1 STACKS FOR LAVS NOT SIZED
 CORRECTLY. MAXIMUM 10 DFU'S ON 2" STACK
 WITH 3 BRANCH INTERVALS OR LESS. 18 DFU
 SHOWN. TABLE 710.1(2).
 10B) SHTS P3.19 & P6.1 FULL OPEN VALVES
 REQUIRED ON THE WATER DISTRIBUTION
 SUPPLY PIPE AT THE ENTRANCE INTO THE
 STRUCTURE, SECTION 606.1(2), AND ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE,
 SECTION 606.1(4).
 11B) SHT P6.1 WATER LINE TO TICKET BOOTH
 NOT SHOWN ON THE WATER RISER DIAGRAM. -
 WATER LINE BY COL. X7 NOT SHOWN ON THE
 WATER RISER DIAGRAM. -DOES NOT REFLECT
 THE WATER PIPING SHOWN ON SHT P3.1A BY
 COL. LINES B/X1!!! THRU A"/X1.
  
 REVIEW BY KEN STEVENS