Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop M
Sequence Number 3
Notes
Date Text
2005-03-25 00:00:00DENIED:
 RESPONSE TO COMMENT FROM REVIEW DATED
 8-28-04:CONDENSATE INDICATED ON THE
 PLUMBING PLANS.REFERENCE COMMENTS BY
 KEN STEVENS, PLUMBING PLAN REVIEW;
 CONDENSATE AND STORM ARE INDICATED INTO
 THE SANITARY.
  
 2.PROVIDE PIPING MATERIAL FOR THE
 CONDENSER WATER PIPING.PLAN SHEET M0.2
 ONLY INDICATES PIPE MATERIAL FOR THE
 REFRIGERANT AND CONDENSATE PIPING.
  
 3.SEE COMMENT #6 BY JIM WITMER
 BUILDING PLAN REVIEW; VENTILATION FOR
 THE GARAGE.
  
 4.PLEASE NOTE, PLAN SHEET M2.1A
 INDICATES ENCLOSED GARAGE, PER 2001 FBC
 411.4.2 THE MECHANICAL SYSTEM SHALL BE
 CAPABLE OF PROVIDING AT LEAST 6 AIR
 CHANGES PER HOUR FOR EACH LEVEL.PLAN
 INDICATES EF-6 FOR THE EXHAUST BUT DOES
 NOT ADDRESS HOW THE AIR MAKE UP WILL BE
 ACHIEVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.