Plan Review Notes For Permit 04042022 |
Permit Number |
04042022 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-03-25 00:00:00 | DENIED: | | RESPONSE TO COMMENT FROM REVIEW DATED | | 8-28-04:CONDENSATE INDICATED ON THE | | PLUMBING PLANS.REFERENCE COMMENTS BY | | KEN STEVENS, PLUMBING PLAN REVIEW; | | CONDENSATE AND STORM ARE INDICATED INTO | | THE SANITARY. | | | | 2.PROVIDE PIPING MATERIAL FOR THE | | CONDENSER WATER PIPING.PLAN SHEET M0.2 | | ONLY INDICATES PIPE MATERIAL FOR THE | | REFRIGERANT AND CONDENSATE PIPING. | | | | 3.SEE COMMENT #6 BY JIM WITMER | | BUILDING PLAN REVIEW; VENTILATION FOR | | THE GARAGE. | | | | 4.PLEASE NOTE, PLAN SHEET M2.1A | | INDICATES ENCLOSED GARAGE, PER 2001 FBC | | 411.4.2 THE MECHANICAL SYSTEM SHALL BE | | CAPABLE OF PROVIDING AT LEAST 6 AIR | | CHANGES PER HOUR FOR EACH LEVEL.PLAN | | INDICATES EF-6 FOR THE EXHAUST BUT DOES | | NOT ADDRESS HOW THE AIR MAKE UP WILL BE | | ACHIEVED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|