Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2005-03-29 00:00:00DENIED
  
 1) ELECTRICAL DRAWINGS-
 1) PLEASE BE ADVISED THAT YOUR COMMENTS
 ARE NOT REFLECTED AS REVISIONS ON THESE
 PLANS. IN ADDITION TO YOUR REVIEW NOTES,
 PLEASE PROVIDE ALL CHANGES ONTO THE
 PLANS FOR FURTHER REVIEW.
  
 2) CONSTUCTION DRAWINGS-
 1) PLEASE BE ADVISED THAT YOUR COMMENTS
 ARE NOT REFLECTED AS REVISIONS ON THESE
 PLANS. IN ADDITION TO YOUR REVIEW NOTES,
 PLEASE PROVIDE ALL CHANGES ONTO THE
 PLANS FOR FURTHER REVIEW.
  
 3) FIRE ALARM DRAWINGS-
 1) PLEASE BE ADVISED THAT THE CITY OF
 WEST PALM BEACH REQUIRES THE DUCT SMOKE
 DETECTORS TO SOUND A GENERAL FIRE ALARM
 WHEN ACTIVATED.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED FOR FIRE ALARM SYSTEM.
  
 FIRE SPRINKLER DRAWINGS-
 1) PLANS SHOW NO SPRINKLER COVERAGE IN
 THE FIRST FLOOR ELECTRICAL ROOM. PLEASE
 EXPLAIN WHAT EXCEPTIONS ARE BEING
 FOLLOWED.
  
 2) SITE PLAN DOES NOT SHOW WHAT ACCESS
 IS PROVIDED FOR THE FIRE DEPARTMENT
 CONNECTION.
  
 3) THE FIRE DEPARTMENT CONNECTION SHALL
 BE LOCATED NO FURTHER THAN 150 FEET FROM
 THE CLOSEST FIRE HYDRANT.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
  