2005-03-29 00:00:00 | DENIED |
| |
| 1) ELECTRICAL DRAWINGS- |
| 1) PLEASE BE ADVISED THAT YOUR COMMENTS |
| ARE NOT REFLECTED AS REVISIONS ON THESE |
| PLANS. IN ADDITION TO YOUR REVIEW NOTES, |
| PLEASE PROVIDE ALL CHANGES ONTO THE |
| PLANS FOR FURTHER REVIEW. |
| |
| 2) CONSTUCTION DRAWINGS- |
| 1) PLEASE BE ADVISED THAT YOUR COMMENTS |
| ARE NOT REFLECTED AS REVISIONS ON THESE |
| PLANS. IN ADDITION TO YOUR REVIEW NOTES, |
| PLEASE PROVIDE ALL CHANGES ONTO THE |
| PLANS FOR FURTHER REVIEW. |
| |
| 3) FIRE ALARM DRAWINGS- |
| 1) PLEASE BE ADVISED THAT THE CITY OF |
| WEST PALM BEACH REQUIRES THE DUCT SMOKE |
| DETECTORS TO SOUND A GENERAL FIRE ALARM |
| WHEN ACTIVATED. |
| |
| 2) SEPARATE SHOP DRAWINGS AND PERMIT IS |
| REQUIRED FOR FIRE ALARM SYSTEM. |
| |
| FIRE SPRINKLER DRAWINGS- |
| 1) PLANS SHOW NO SPRINKLER COVERAGE IN |
| THE FIRST FLOOR ELECTRICAL ROOM. PLEASE |
| EXPLAIN WHAT EXCEPTIONS ARE BEING |
| FOLLOWED. |
| |
| 2) SITE PLAN DOES NOT SHOW WHAT ACCESS |
| IS PROVIDED FOR THE FIRE DEPARTMENT |
| CONNECTION. |
| |
| 3) THE FIRE DEPARTMENT CONNECTION SHALL |
| BE LOCATED NO FURTHER THAN 150 FEET FROM |
| THE CLOSEST FIRE HYDRANT. |
| |
| 4) SEPARATE SHOP DRAWINGS AND PERMIT IS |
| REQUIRED FOR FIRE SPRINKLER SYSTEM. |
| |
| |
| MIKE WENNERGREN, A/CAPTAIN |
| WPBFR(561) 835-2910 |