2005-03-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE FIRE PUMP MOTER DESIGN
 LETTER SO THAT LOCKEE ROTOR CURRENT CAN
 BE DETERMINED FOR THE DISCONNECTING
 MEANS. I COULD NOT FIND THE DESIGNATION
 IN THE SPECS.
  
 2} INDICATE THAT THE FIRE PUMP
 CONTROLLER HAS AN EXTERNAL MEANS OF
 DISCONNECT ON THE PLAN ALSO INDICATE
 AMPERAGE RATING OF SAME ON PLANS. AGAIN
 THESE WERE NOT CLEAR IN THE SPECS.
  
 3} CORRELATE THE HP OF THE FIRE PUMP
 RATING ON THE PLAN WITH THE ONE IN THE
 SPECS.
  
 4} THERE ARE STILL NO LOAD OR BREAKER
 SIZES IN MSBA FOR CIRCUITS 7,8&9.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW