Date |
Text |
2005-03-18 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04042022 |
| ADD: 477 3RD ST/ 444 W RAILROAD AVE |
| CONT: PLAN REVIEW |
| CONTACT: WEST RAILROAD LIMITED |
| PROJECT SUPERVISOR: PATTI LUDLOW |
| TEL: (561)368-2544 EXT. 22 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 3RD PLAN REVIEW |
| ACTION: DENIED |
| |
| NOTE: WHEN APPLYING FOR A PERMIT, (3) |
| SETS OF PLANS, AND SUPPORTING DOCUMENTS |
| SHALL BE REQUIRED, SIGNED & SEALED IF |
| PRODUCED BY A DESIGN PROFESIONAL. |
| |
| NOTE: PLEASE PROVIDE A RESPONSE SHEET |
| INDICATING WHERE THE CORECTION CAN BE |
| FOUND, THIS WILL GREATLY HELP THE TURN |
| AROUND TIME OF YOUR PLAN REVIEW. |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2)FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| SRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| TION PLAN PREPARED BY THE ENGINEER OF |
| RECORD. THE STRUCTURAL INSPECTION PLAN |
| MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| CY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| IC INSPECTION PROCEDURES AND SCHEDULES |
| SO THAT THE BUILDING CAN BE ADEQUATELY |
| INSPECTED FOR COMPLIANCE WITH THE |
| PERMITTED DOCUMENTS. |
| |
| 3)W.P.B. AMENDMENT 105.13.4.4 ALL |
| PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CON- |
| TAIN A STATEMENT THAT, TO THE BEST OF |
| THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY WITH |
| THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 4)WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 5) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL |
| IS NOT DEFINITLY KNOWN OR IS IN QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL |
| PROPERLY LICENSED IN THE STATE OF |
| FLORIDA. |
| WHEN SUBMITTING FOR PERMIT (3) SETS OF |
| SEALED SURVEYS WILL BE REQUIRED. |
| |
| 6) PARKING GARAGE TO BE CONSIDERED A |
| OPEN PARKING GARAGE, THE AMOUNT OF |
| OPENINGS SHALL MEET THE REQUIREMENTS OF |
| 411.3.2(2) WITH THE EXCEPTION OF THE |
| FOURTH FLOOR. WITH NO WINDOWS INDICATED |
| ON THE NORTH WALL OF THE FOURTH FLOOR |
| THE THE AMOUNT OF OPENINGS FOR THE FORTH |
| FLOOR IS 19.4% NOT THE REQUIRED 20%. |
| |
| 7) 705.7.1 JOINTS INSTALLED IN OR BE- |
| TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| APPROVED FIRE RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE |
| FOR A PERIOD NOT LESS THAN THE RE- |
| QUIRED FIRE RESISTANCE RATING OF THE |
| WALL, FLOOR OR FLOOR IN OR BETWEEN |
| WHICH IT IS INSTALLED. |
| |
| 8) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 9)THE TICKET BOOTH MANUFACTURED BY |
| MARDAN FABRICATORS VISTA SERIES- HANDI- |
| CAPPED ACCESSIBLE BOOTH WILL REQUIRE |
| PLAN SUBMITTAL WITH STATE APPROVAL FROM |
| DCA PREMANUFACTURED BUILDINGS. |
| |
| 10) PLANS APPEAR TO BE MISSING SHEETS: |
| A52.01 |
| A55.01 |
| A61.01 |
| A62.01 |
| PLEASE PLACE THESE PAGES IN THE ORDER |
| THEY SHOULD READ, NOT AT THE BACK OF THE |
| PLANS!!!!!! |
| |
| 11) REVISIT THE DOOR RATINGS FOR: |
| A) DOORS BETWEEN THE GARAGE AND OFFICE |
| CORRIDOR ( 1 1/2 HR) TABLE 704.1 |
| B) REFUSE CHUTE ACCESS DOORS (1 |
| HR)705.1.2 |
| C) STAIRWELL SHAFT DOORS > 4 STORIES |
| (1 1/2 HR) TABLE 705.1.2 |
| |
| 12)FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS |
| B) EXTERIOR DOORS |
| C) LOUVER |
| D) SKYLIGHTS |
| E) TRUSS ANCHORS |
| F) ROOF ASEMBLIES |
| G) RAILINGS |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 13) 2ND REQUEST FOR INFORMATION, TABLE |
| 600 TYPE II BUILDING, FIRE PROTECTION |
| RATING FOR COLUMNS, BEAMS, GIRDERS, |
| FLOORS & FLOOR/CEILING ASSEMBLIES AND |
| ROOFS OR ROOF/CEILING ASSEMBLIES. |
| RESPONCE IS "SEE STRUCTURAL COMMENTS", |
| WHERE? |
| |
| 14)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |
| |
| |
| |
| |
| |
| |