Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-09-16 00:00:001) NO EXIT SIGN OR EMERGENCY LIGHTS IN
 CAFE OR BANK.
  
 2) AN EXIT SIGN ON THE FIRST FLOOR
 LIGHTING PLAN DIRECTS PEOPLE FROM THE
 DRIVE THRU AREA TO WHERE.
  
 3) EXIT SIGN MISSING FROM GARAGE STAIR
 ON FIRST FLOOR LIGHTING PLAN.
  
 4) PLEASE EXPLAIN EXITING ARRANGEMENT
 FOR THE NORTHWEST OFFICE AND NORTHEAST
 OFFICE, THIRD FLOOR.
  
 5) PLEASE EXPLAIN EXITING RATIONALE
 FROM THIRD FLOOR BRIDGE FROM COURTHOUSE
 COMMONS BUILDING TO THE EXISTING
 PARKING GARAGE. WHO PRESENTLY OWNS
 THE EXISTING PARKING GARAGE AND HOW
 DO YOU EXIT PEOPLE ONTO OTHER PERSONS
 PROPERTY.
  
 6) EXIT SIGN APPEARS TO BE MISSING FROM
 CENTER STAIR 4TH FLOOR LIGHTING PLAN.
  
 7) EMERGENCY LIGHTING MISSING AT EXIT
 DOORS ON FIFTH FLOOR LIGHTING PLAN (B).
  
 8) EXIT SIGNS MISSING FROM ROOF LIGHTING
 PLAN.
  
 9) FIRE ALARM NOTES # 17 AND 19 ARE
 INCORRECT. DUCT SMOKE DETECTORS WHEN
 ACTIVATED SHALL INITIATE AN ALARM NOT
 A SUPERVISORY SIGNAL. FIRE ALARM
 CIRCUITS SHALL BE CLASS A OR STYLE D
 OR BE FULLY ADDRESSABLE. FIRE ALARM
 SYSTEM SHALL BE UL LISTED FOR CENTRAL
 STATION SERVICE.
  
 10) FIRE ALARM INITIATING DEVICES
 APPEAR TO BE MISSING FROM THE ROOF
 ELEVATOR MECHANICAL ROOM.
  
 11) PLEASE PROVIDE UL NUMBERS FOR
 ALL FIRE RATED WALLS.
  
 12) ALL RATED WALLS SHOULD HAVE DASHED
 LINES INDICATING ONE HOUR OR TWO
 HOUR ASSEMBLIES.
  
 13) PLEASE VERIFY ALL EXIT DOORS
 SWINGS.
  
 14) DOORS 6A1 AND 6A2 ON ROOF SWING
 IN THE WRONG DIRECTION.
  
 15) ALL NEW RAMPS AND STAIRS SHALL
 HAVE HANDRAILS ON BOTH SIDES.
  
 16) ELEVATOR WARNING SIGNS REQUIRED.
  
 17) THE FIRE DEPARTMENT CONNECTION IS
 LOCATED ON THE WRONG SIDE OF THE
 BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910