2004-09-16 00:00:00 | 1) NO EXIT SIGN OR EMERGENCY LIGHTS IN |
| CAFE OR BANK. |
| |
| 2) AN EXIT SIGN ON THE FIRST FLOOR |
| LIGHTING PLAN DIRECTS PEOPLE FROM THE |
| DRIVE THRU AREA TO WHERE. |
| |
| 3) EXIT SIGN MISSING FROM GARAGE STAIR |
| ON FIRST FLOOR LIGHTING PLAN. |
| |
| 4) PLEASE EXPLAIN EXITING ARRANGEMENT |
| FOR THE NORTHWEST OFFICE AND NORTHEAST |
| OFFICE, THIRD FLOOR. |
| |
| 5) PLEASE EXPLAIN EXITING RATIONALE |
| FROM THIRD FLOOR BRIDGE FROM COURTHOUSE |
| COMMONS BUILDING TO THE EXISTING |
| PARKING GARAGE. WHO PRESENTLY OWNS |
| THE EXISTING PARKING GARAGE AND HOW |
| DO YOU EXIT PEOPLE ONTO OTHER PERSONS |
| PROPERTY. |
| |
| 6) EXIT SIGN APPEARS TO BE MISSING FROM |
| CENTER STAIR 4TH FLOOR LIGHTING PLAN. |
| |
| 7) EMERGENCY LIGHTING MISSING AT EXIT |
| DOORS ON FIFTH FLOOR LIGHTING PLAN (B). |
| |
| 8) EXIT SIGNS MISSING FROM ROOF LIGHTING |
| PLAN. |
| |
| 9) FIRE ALARM NOTES # 17 AND 19 ARE |
| INCORRECT. DUCT SMOKE DETECTORS WHEN |
| ACTIVATED SHALL INITIATE AN ALARM NOT |
| A SUPERVISORY SIGNAL. FIRE ALARM |
| CIRCUITS SHALL BE CLASS A OR STYLE D |
| OR BE FULLY ADDRESSABLE. FIRE ALARM |
| SYSTEM SHALL BE UL LISTED FOR CENTRAL |
| STATION SERVICE. |
| |
| 10) FIRE ALARM INITIATING DEVICES |
| APPEAR TO BE MISSING FROM THE ROOF |
| ELEVATOR MECHANICAL ROOM. |
| |
| 11) PLEASE PROVIDE UL NUMBERS FOR |
| ALL FIRE RATED WALLS. |
| |
| 12) ALL RATED WALLS SHOULD HAVE DASHED |
| LINES INDICATING ONE HOUR OR TWO |
| HOUR ASSEMBLIES. |
| |
| 13) PLEASE VERIFY ALL EXIT DOORS |
| SWINGS. |
| |
| 14) DOORS 6A1 AND 6A2 ON ROOF SWING |
| IN THE WRONG DIRECTION. |
| |
| 15) ALL NEW RAMPS AND STAIRS SHALL |
| HAVE HANDRAILS ON BOTH SIDES. |
| |
| 16) ELEVATOR WARNING SIGNS REQUIRED. |
| |
| 17) THE FIRE DEPARTMENT CONNECTION IS |
| LOCATED ON THE WRONG SIDE OF THE |
| BUILDING. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |