 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE INFORMATION AND
 TECHNICAL DATA/SPECIFICATIONS FOR THE
 FIRE PUMP. SUCH INFORMATION SHOULD
 INDICATE COMPLIANCE WITH ARTICLES
 230.76, 230.79, AND 695.4 NEC 2002.
  
 2} WHAT ARE THE DISCONNECTS SHOWN ON
 SHEET E3.1A,ELEVATOR MACHINE ROOM
 DETAIL, USED FOR? THEY ARE BEING FED
 FROM MSBA CIRCUITS 7,8 & 9, THESE
 CIRCUITS SHOW NO LOADS ON THE MSBA
 SCHEDULE.
  
 3} PLEASE ADDRESS COMMENTS ON FIRE
 REVIEW AND SHOW ALL LIGHTING
 CORRECTIONS ON ELECTRICAL SHEETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  