Plan Review Notes For Permit 04042022 |
Permit Number |
04042022 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-09-23 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE PROVIDE INFORMATION AND | | TECHNICAL DATA/SPECIFICATIONS FOR THE | | FIRE PUMP. SUCH INFORMATION SHOULD | | INDICATE COMPLIANCE WITH ARTICLES | | 230.76, 230.79, AND 695.4 NEC 2002. | | | | 2} WHAT ARE THE DISCONNECTS SHOWN ON | | SHEET E3.1A,ELEVATOR MACHINE ROOM | | DETAIL, USED FOR? THEY ARE BEING FED | | FROM MSBA CIRCUITS 7,8 & 9, THESE | | CIRCUITS SHOW NO LOADS ON THE MSBA | | SCHEDULE. | | | | 3} PLEASE ADDRESS COMMENTS ON FIRE | | REVIEW AND SHOW ALL LIGHTING | | CORRECTIONS ON ELECTRICAL SHEETS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|