2007-03-22 11:12:31 | |
| THIS REVIEW, #15 IS CONCERNING CORRIDOR REMOVAL./WRT. |
2007-03-22 09:55:52 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} SHEETS E2.2A, E 2.3A, E2.4A AND E2.5A, THE FLOOR |
| MUST HAVE EGRESS ILLUMINATION PER 7.8.AND 7.9, |
| NFPA-101. PLACE FIXTURES ON PLAN TO SHOW COMPLIANCE. |
| |
| 2} SHEET E3.1A, CIRCUIT L1A-30 TO M1-1, IS LISTED AS A |
| SPARE ON THE SCHEDULE. |
| |
| 3} CIRCUIT L1A-6 TO THE SECURITY ROOM RECEPTACLES ARE |
| INCORRECTLY LISTED AS "MAIL ROOM" ON THE SCHEDULE. |
| |
| 4} NOTE #7 REFERENCES THE ELEVATOR MACHINE ROOM DETAIL |
| WHICH HAS BEEN REMOVED FROM THIS SHEET. NOTE SHOULD BE |
| CORRECTED TO REFLECT THE DETAIL ON THE CORRECT SHEET, |
| E4.1. |
| |
| 5} CIRCUIT L1A-2 NOW LOCATED IN THE ELECTRIC ROOM, IS |
| INCORRECTLY MARKED AS IN THE LOBBY ON THE SCHEDULE. |
| |
| 6}SHEET E3.3A, SHOW THE DOOR ON THE ELECTRICAL ROOM TO |
| INDICATE THE EQUIPMENT IS PROPERLY GUARDED PER 110.27. |
| |
| 7} SHEET E4.1 REVISE THIRD FLOOR ELECTRICAL ROOM TO |
| INCLUDE A DOOR, 110.27 NEC. |
| |
| 8} SHEET E5.1 DOES NOT INDICATE A FEED FOR PANEL "TB" |
| SHOWN ON SHEET E3.1B. IT IS UNDERSTOOD THAT IT WILL BE |
| SUPPLIED WITH THE BOOTH EQUIPMENT AS NOTED ON THE PANEL |
| SCHEDULE BUT NO INDICATION OF FEEDER AND OCP ORIGIN. |
| |
| 9} SHEET E3.1A LISTS THE ELEVATOR MMACHINE ROOM AS A |
| MECHANICAL ROOM, PLEASE CORRELATE. |
| |
| 10} REGARDING SHEET E4.1, THE ELEVATOR MACHINE ROOM IS |
| NOT COMPLETE, THE DISCONNECTS FOR ELEVATORS 4 & 5 ARE |
| NOT SHOWN. |
| |
| 11} E4.1, THE ELEVATOR MACHINE ROOM FOR ELEVATORS 1, 2, |
| AND 3 DOES NOT INCLUDE THE DISCONNECTS FOR SAME. ALSO |
| THOSE DISCONNECTS ARE NOT MARKED WITH CIRCUIT NUMBERS |
| ON SHEET E3.1. PANEL EL1AIS INCORRECTLY LOCATED ON |
| ONE OR THE OTHER SHEET. |
| |
| 13} THE ELECTRICAL ROOM LAYOUT ON E4.1 DOES NOT |
| CORRELATE WITH SAME ON SHEET E3.1A. |
| |
| NOTE: SHEETS E2.1A, E2.6A, E3.1A, E3.2A, E3.3A, E3.4A, |
| E3.5A AND E5.1, HAVING BEEN REVIEWED AS COMPLIANT AND |
| HAVE BEEN STAMPED AND MADE PART OF THE FILED DOCUMENTS. |
| TWO SETS HAVE BEEN STAMPED FOR RETURN TO TO THE |
| CONTRACTOR. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW. |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| [email protected] |