Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop E
Sequence Number 15
Notes
Date Text
2007-03-22 11:12:31 
 THIS REVIEW, #15 IS CONCERNING CORRIDOR REMOVAL./WRT.
2007-03-22 09:55:52 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHEETS E2.2A, E 2.3A, E2.4A AND E2.5A, THE FLOOR
 MUST HAVE EGRESS ILLUMINATION PER 7.8.AND 7.9,
 NFPA-101. PLACE FIXTURES ON PLAN TO SHOW COMPLIANCE.
  
 2} SHEET E3.1A, CIRCUIT L1A-30 TO M1-1, IS LISTED AS A
 SPARE ON THE SCHEDULE.
  
 3} CIRCUIT L1A-6 TO THE SECURITY ROOM RECEPTACLES ARE
 INCORRECTLY LISTED AS "MAIL ROOM" ON THE SCHEDULE.
  
 4} NOTE #7 REFERENCES THE ELEVATOR MACHINE ROOM DETAIL
 WHICH HAS BEEN REMOVED FROM THIS SHEET. NOTE SHOULD BE
 CORRECTED TO REFLECT THE DETAIL ON THE CORRECT SHEET,
 E4.1.
  
 5} CIRCUIT L1A-2 NOW LOCATED IN THE ELECTRIC ROOM, IS
 INCORRECTLY MARKED AS IN THE LOBBY ON THE SCHEDULE.
  
 6}SHEET E3.3A, SHOW THE DOOR ON THE ELECTRICAL ROOM TO
 INDICATE THE EQUIPMENT IS PROPERLY GUARDED PER 110.27.
  
 7} SHEET E4.1 REVISE THIRD FLOOR ELECTRICAL ROOM TO
 INCLUDE A DOOR, 110.27 NEC.
  
 8} SHEET E5.1 DOES NOT INDICATE A FEED FOR PANEL "TB"
 SHOWN ON SHEET E3.1B. IT IS UNDERSTOOD THAT IT WILL BE
 SUPPLIED WITH THE BOOTH EQUIPMENT AS NOTED ON THE PANEL
 SCHEDULE BUT NO INDICATION OF FEEDER AND OCP ORIGIN.
  
 9} SHEET E3.1A LISTS THE ELEVATOR MMACHINE ROOM AS A
 MECHANICAL ROOM, PLEASE CORRELATE.
  
 10} REGARDING SHEET E4.1, THE ELEVATOR MACHINE ROOM IS
 NOT COMPLETE, THE DISCONNECTS FOR ELEVATORS 4 & 5 ARE
 NOT SHOWN.
  
 11} E4.1, THE ELEVATOR MACHINE ROOM FOR ELEVATORS 1, 2,
 AND 3 DOES NOT INCLUDE THE DISCONNECTS FOR SAME. ALSO
 THOSE DISCONNECTS ARE NOT MARKED WITH CIRCUIT NUMBERS
 ON SHEET E3.1. PANEL EL1AIS INCORRECTLY LOCATED ON
 ONE OR THE OTHER SHEET.
  
 13} THE ELECTRICAL ROOM LAYOUT ON E4.1 DOES NOT
 CORRELATE WITH SAME ON SHEET E3.1A.
  
 NOTE: SHEETS E2.1A, E2.6A, E3.1A, E3.2A, E3.3A, E3.4A,
 E3.5A AND E5.1, HAVING BEEN REVIEWED AS COMPLIANT AND
 HAVE BEEN STAMPED AND MADE PART OF THE FILED DOCUMENTS.
 TWO SETS HAVE BEEN STAMPED FOR RETURN TO TO THE
 CONTRACTOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.