2007-01-23 10:57:15 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} PLEASE NOTE ALL CHANGES WITH CLOUDS AND DELTAS. |
| REMOVE CLOUDS AND DELTAS FROM PREVIOUS REVIEWS FOR |
| CLARITY. THE POLE MOUNTING DETAIL ON SHEET EO.1 IS NOT |
| SHOWN AS A REVISION. SUBMIT THOSE REVISIONS WITH |
| SPECIFICATIONS AND ENGINEERING AS REVISIONS FOR THE |
| POLES. |
| |
| 2} SHEET E2.1A, CIRCUIT EL1B-6 MARKED FOR THE ELEVATOR |
| SHAFT LIGHTING IS INDICATED AS A SPARE ON THE PANEL |
| SCHEDULE (E6.1), CIRCUITS 5 & 7 LISTED AS PIT LIGHTS ON |
| THE SCHEDULE, |
| |
| 3}THE ELEVATOR PIT RECEPTACLE IS ALSO LISTED ON |
| CIRCUIT EL1B-6 ON SHEET E3.1A, THAT CIRCUIT IS #4 ON |
| THE SCHEDULE. |
| NOTE: THE ELEVATOR CONTROL CIRCUIT WAS REMOVED |
| FROM THE PANEL SCHEDULE(S). |
| |
| 4} THE TRANSFORMER IN THE ELECTRICAL ROOM ON SHEET |
| E2.1A IS MISMARKED AS PANEL H1A. |
| |
| 5} SHEET E2.3A, THE CORRIDOR LIGHTING IS NOT CIRCUITED |
| ( ELEVATOR LOBBY CORRIDOR). |
| |
| 6} SHEET E2.5A, THE ROOM MUST HAVE EGRESS ILLUMINATION |
| PER 7.8.1.3NFPA-101. PLACE FIXTURES ON PLAN TO SHOW |
| COMPLIANCE. |
| |
| 7} SHEET E3.1A, CIRCUIT L1A-30 TO M1-1, IS LISTED AS A |
| SPARE ON THE SCHEDULE. |
| |
| 8} CIRCUIT L1A-6 TO THE SECURITY ROOM RECEPTACLES ARE |
| INCORRECTLY LISTED AS "MAIL ROOM" ON THE SCHEDULE. |
| |
| 9} THE DOMESTIC WATER PUMPS (2 EACH) ARE SHOWN ON |
| CIRCUIT H1A-31, 33, 35. THE PANEL SCHEDULE SHOWS |
| CIRCUITS 37, 39, 41 AS FUTURE . PLEASE CLARIFY THE |
| NUMBER OF PUMPS TO BE INSTALLED UNDER THIS PERMIT AND |
| THE CIRCUITDESIGNATION OF SAME. |
| |
| 10} NOTE #7 REFERENCES THE ELEVATOR MACHINE ROOM DETAIL |
| WHICH HAS BEEN REMOVED FROM THIS SHEET. NOTE SHOULD BE |
| CORRECTED TO REFLECT THE DETAIL ON THE CORRECT SHEET, |
| E4.1. |
| |
| 11} CIRCUIT L1A-2 NOW LOCATED IN THE ELECTRIC ROOM, IS |
| INCORRECTLY MARKED AS IN THE LOBBY ON THE SCHEDULE. |
| |
| 12}SHEET E3.3A, SHOW THE DOOR ON THE ELECTRICAL ROOM TO |
| INDICATE THE EQUIPMENT IS PROPERLY GUARDED PER 110.27. |
| |
| 13} REVISE AND SUBMIT SHEET E2.3A TO REFLECT THE |
| CHANGES IN THE FLOOR PLAN ON E3.3A. |
| |
| 14} SHEET E4.1 REVISE THIRD FLOOR ELECTRICAL ROOM TO |
| INCLUDE A DOOR, 110.27 NEC. |
| |
| 15} SHEET E5.1 DOES NOT INDICATE A FEED FOR PANEL "TB" |
| SHOWN ON SHEET E3.1B. IT IS UNDERSTOOD THAT IT WILL BE |
| SUPPLIED WITH THE BOOTH EQUIPMENT AS NOTED ON THE PANEL |
| SCHEDULE BUT NO INDICATION OF FEEDER AND OCP ORIGIN. |
| |
| NOTE: SHEETS E2.4A, E3.1B AND E7.1 HAVING BEEN REVIEWED |
| AS COMPLIANT AND HAVE BEEN STAMPED AND MADE PART OF THE |
| FILED DOCUMENTS. TWO SHEETS HAVE BEEN STAMPED FOR |
| RETURN TO TO THE CONTRACTOR. SHEET E3.4A MUST ALSO BE |
| REVISED TO MATCH THE CHANGES ON E2.4A. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW. |