Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop E
Sequence Number 13
Notes
Date Text
2007-01-23 10:57:15 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE ALL CHANGES WITH CLOUDS AND DELTAS.
 REMOVE CLOUDS AND DELTAS FROM PREVIOUS REVIEWS FOR
 CLARITY. THE POLE MOUNTING DETAIL ON SHEET EO.1 IS NOT
 SHOWN AS A REVISION. SUBMIT THOSE REVISIONS WITH
 SPECIFICATIONS AND ENGINEERING AS REVISIONS FOR THE
 POLES.
  
 2} SHEET E2.1A, CIRCUIT EL1B-6 MARKED FOR THE ELEVATOR
 SHAFT LIGHTING IS INDICATED AS A SPARE ON THE PANEL
 SCHEDULE (E6.1), CIRCUITS 5 & 7 LISTED AS PIT LIGHTS ON
 THE SCHEDULE,
  
 3}THE ELEVATOR PIT RECEPTACLE IS ALSO LISTED ON
 CIRCUIT EL1B-6 ON SHEET E3.1A, THAT CIRCUIT IS #4 ON
 THE SCHEDULE.
 NOTE: THE ELEVATOR CONTROL CIRCUIT WAS REMOVED
 FROM THE PANEL SCHEDULE(S).
  
 4} THE TRANSFORMER IN THE ELECTRICAL ROOM ON SHEET
 E2.1A IS MISMARKED AS PANEL H1A.
  
 5} SHEET E2.3A, THE CORRIDOR LIGHTING IS NOT CIRCUITED
 ( ELEVATOR LOBBY CORRIDOR).
  
 6} SHEET E2.5A, THE ROOM MUST HAVE EGRESS ILLUMINATION
 PER 7.8.1.3NFPA-101. PLACE FIXTURES ON PLAN TO SHOW
 COMPLIANCE.
  
 7} SHEET E3.1A, CIRCUIT L1A-30 TO M1-1, IS LISTED AS A
 SPARE ON THE SCHEDULE.
  
 8} CIRCUIT L1A-6 TO THE SECURITY ROOM RECEPTACLES ARE
 INCORRECTLY LISTED AS "MAIL ROOM" ON THE SCHEDULE.
  
 9} THE DOMESTIC WATER PUMPS (2 EACH) ARE SHOWN ON
 CIRCUIT H1A-31, 33, 35. THE PANEL SCHEDULE SHOWS
 CIRCUITS 37, 39, 41 AS FUTURE . PLEASE CLARIFY THE
 NUMBER OF PUMPS TO BE INSTALLED UNDER THIS PERMIT AND
 THE CIRCUITDESIGNATION OF SAME.
  
 10} NOTE #7 REFERENCES THE ELEVATOR MACHINE ROOM DETAIL
 WHICH HAS BEEN REMOVED FROM THIS SHEET. NOTE SHOULD BE
 CORRECTED TO REFLECT THE DETAIL ON THE CORRECT SHEET,
 E4.1.
  
 11} CIRCUIT L1A-2 NOW LOCATED IN THE ELECTRIC ROOM, IS
 INCORRECTLY MARKED AS IN THE LOBBY ON THE SCHEDULE.
  
 12}SHEET E3.3A, SHOW THE DOOR ON THE ELECTRICAL ROOM TO
 INDICATE THE EQUIPMENT IS PROPERLY GUARDED PER 110.27.
  
 13} REVISE AND SUBMIT SHEET E2.3A TO REFLECT THE
 CHANGES IN THE FLOOR PLAN ON E3.3A.
  
 14} SHEET E4.1 REVISE THIRD FLOOR ELECTRICAL ROOM TO
 INCLUDE A DOOR, 110.27 NEC.
  
 15} SHEET E5.1 DOES NOT INDICATE A FEED FOR PANEL "TB"
 SHOWN ON SHEET E3.1B. IT IS UNDERSTOOD THAT IT WILL BE
 SUPPLIED WITH THE BOOTH EQUIPMENT AS NOTED ON THE PANEL
 SCHEDULE BUT NO INDICATION OF FEEDER AND OCP ORIGIN.
  
 NOTE: SHEETS E2.4A, E3.1B AND E7.1 HAVING BEEN REVIEWED
 AS COMPLIANT AND HAVE BEEN STAMPED AND MADE PART OF THE
 FILED DOCUMENTS. TWO SHEETS HAVE BEEN STAMPED FOR
 RETURN TO TO THE CONTRACTOR. SHEET E3.4A MUST ALSO BE
 REVISED TO MATCH THE CHANGES ON E2.4A.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]