Plan Review Notes For Permit 04042022 |
Permit Number |
04042022 |
|
Review Stop |
M |
Sequence Number |
12 |
|
Notes |
Date |
Text |
2007-03-06 15:54:00 | REVISIONS SUBMITTED FOR PAGES M2.1A, M2.2, M2.3, M2.4, | | M2.5 | | | | PG M2.2 DENIED: THE FIRE DAMPER EXCEPTION AS NOTED ON | | PLAN DOES NOT APPLY TO THIS PROJECT AS IT WAS PERMITTED | | UNDER FBC 2001. THE CODE SECTION CITED DOES NOT RELATE | | TO FBC,M 2001. PLEASE CORRECT AND RESUBMIT. | | | | PG M2.5 CITES THE SAME CODE SECTION. HOWEVER, THE FIRE | | DAMPERS IN QUESTION ARE INSTALLED AND SHOWN ON PLAN. | | SINCE THE EXCEPTION IS NOT BEING CLAIMED, THIS PAGE HAS | | PASSED REVIEW. | | | | ALL OTHER MECHANICAL PLAN REVIEW COMMENTS AND PROVISOS | | HAVE BEEN SATISFIED TO THIS POINT. | | | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|