Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop M
Sequence Number 12
Notes
Date Text
2007-03-06 15:54:00REVISIONS SUBMITTED FOR PAGES M2.1A, M2.2, M2.3, M2.4,
 M2.5
  
 PG M2.2 DENIED: THE FIRE DAMPER EXCEPTION AS NOTED ON
 PLAN DOES NOT APPLY TO THIS PROJECT AS IT WAS PERMITTED
 UNDER FBC 2001. THE CODE SECTION CITED DOES NOT RELATE
 TO FBC,M 2001. PLEASE CORRECT AND RESUBMIT.
  
 PG M2.5 CITES THE SAME CODE SECTION. HOWEVER, THE FIRE
 DAMPERS IN QUESTION ARE INSTALLED AND SHOWN ON PLAN.
 SINCE THE EXCEPTION IS NOT BEING CLAIMED, THIS PAGE HAS
 PASSED REVIEW.
  
 ALL OTHER MECHANICAL PLAN REVIEW COMMENTS AND PROVISOS
 HAVE BEEN SATISFIED TO THIS POINT.
  