 REVISION DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHEET E2.3A THE LUMINAIRES ADDED TO THE CORRIDOR ATR
 NOT CIRCUITED. PLEASE INDICATE CIRCUIT NUMBERS AND
 PANEL DESIGNATION. 106.3.5.1FBC AS AMMENDED.
  
 2} THE ROLL UP DOOR CIRCUITS ON SHEET E3.1A AND E3.2B
 HAVE NOT BEEN ADDED TO THE PANEL SCHEDULE, AND
 THEREFORE THE CALCULATIIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.