Plan Review Notes For Permit 04042022 |
Permit Number |
04042022 |
|
Review Stop |
E |
Sequence Number |
12 |
|
Notes |
Date |
Text |
2007-01-11 16:51:06 | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} SHEET E2.3A THE LUMINAIRES ADDED TO THE CORRIDOR ATR | | NOT CIRCUITED. PLEASE INDICATE CIRCUIT NUMBERS AND | | PANEL DESIGNATION. 106.3.5.1FBC AS AMMENDED. | | | | 2} THE ROLL UP DOOR CIRCUITS ON SHEET E3.1A AND E3.2B | | HAVE NOT BEEN ADDED TO THE PANEL SCHEDULE, AND | | THEREFORE THE CALCULATIIONS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|