Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop B
Sequence Number 11
Notes
Date Text
2007-01-05 08:44:09BUILDING PLAN REVIEW
 PERMIT: 04042022
 ADD: 444 W RAILROAD AVE
 CONT: PBM DEVELOPMENT
 TEL: (954)868-5944
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
  
 1) PBM DEVELOPMENT IS ACTING AS A ARCHITECTURAL FIRM,
 EITHER PBM DEVELOPMENT NEEDS TO AQUIRE A CERTIFICATE
 OF AUTHORIZATION OR REMOVE THEIR NAME FROM THE
 TITLEBLOCK
 AND USE THE LICENSED ARCHITECT DOMINICK SCARFO INTHE
 TITLE
 BLOCK AS AN INDIVDUAL.
  
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 2) THE SECOND ISSUE WITH THIS SERIES OF REVISIONS IS :
 A.31.03 THE THIRD FLOOR CORRIDOR, A.31.04 FOURTH FLOOR,
 THE NEW CORRIDOR
 WALLS ANDDOORS DO NOT INDICATE ANY RATINGS. THE
 NARRATIVE AND THE ARCHITECTURAL NOTES ON SHEET A.00.00
 HAVE A PHRASE " CORRIDOR RATED" DRYWALL PARTITIONS.
 THERE IS A DIFFERENCE IN CORRIDOR RATINGS UNDER THE
 2001FBC AND 2004 FBC. THE ISSUED PERMIT SET OF PLANS
 UNDER THE 2001 FBC INDICATE WALL TAG (102)HR FIRE
 RATED CORRIDORS AND
 20 MINUTE DOORS. THE DOORSIN THE NEWLY ADDED
 CORRIDORS DO NOT HAVE ANY
 IDENTIFICATION MARKERS EITHER.
  
 PLEASE PROVIDE WALL AND DOOR MARKER INDICATING THEIR
 FIRE RATINGS.
  
 3) A.41.03 REVISION# 7 THERE IS NO CEILING HEIGHT
 INDICATORS
 ALTHOUGH NOTE# 4AS NOTED.ADDITIONAL INFORMATION
 REQUIRED. 106.1.2.
  
 4A) A.41.04 REVISION# 1 NEW CEILING DESIGN IN LOBBY, NO
  
 INFORMATION AS TO HEIGHT OR TYPE OF MATERIALS TO BE
 USED.
 ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 4B) A.41.04 REVISION# 2THERE IS NO CEILING HEIGHT
 INDICATORS
 ALTHOUGH NOTE# 4AS NOTED.ADDITIONAL INFORMATION
 REQUIRED. 106.1.2.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved