2004-05-25 00:00:00PROPOSED BUILDING DOES NOT MEET THE
 SPIRIT AND INTENT OF THE DOWNTOWN MASTER
 PLAN - GOAL TO PROVIDE CONNECTIVITY FROM
 NW NEIGHBORHOOD TO REST OF CITY.ALSO:
 1) PEDESTRIAN BRIDGE REQUIRES CITY COM.
 APPROVAL BY RESOLUTION.PLANNING WILL
 NOT SUPPORT.
 2)CANTILEVERED CANOPY & OTHER ELEMENTS
 THAT OVERHAND THE ROW REQUIRE CITY COM.
 APPROVAL BY RESOLUTION.PLANNING WILL
 NOT SUPPORT.
 3) 94-107(B)(6) CAFE DOOR MUST BE ON
 FRONTAGE LINE
 4) 94-107(B)(7) CONFIRM THAT 8FT. MIN.
 FOR SIDEWALK IS PROVIDED AND THAT ON-
 STREET PARKING IS FEASIBLE.
 5) 94-107(D)(4) ACCESS FROM ELEVATORS
 DOES NOT ALLW ENTRY TO THE PARKING
 GARAGE FROM THE FRONTAGE LINE
 6) 94-107(E)(1) CONFIRM TINTING LEVELS A
 ND COLOR OF GLASS
 7) 94-107(E)(4) ELEVATIONS OF PARKING
 GARAGE ARE ILLEGIBLE - PLEASE INDICATE
 MORE CLEARLY THE OPENINGS ON THE FACADES
 AND PROVIDE CALCULATIONS TO DEMONSTRATE
 COMPLIANCE WITH 45% MAX.