Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
  
 1) SECTION 104.2.2 OFFICIAL SEAL SHALL
 BE AFFIXED TO PLANS WITH SIGNATURE, DATE
 AND TITLE BLOCK.
 2) SHT A.00.03 SITE CALCULATIONS FOR
 MINIMUM FIXTURES PER TABLES 1003.1 AND
 403.1. SHOW GROSS AREA FOR BANK AND CAFE
 ON THE FIRST FLOOR, AND FOR OFFICE SPACE
 ON 2ND THRU 5TH FLOORS.
 3) PLANS SHALL BE ROUTED TO DBPR HOTEL &
 RESTURANT DIVISION FOR REVIEW. PLANS
 SHALL BE STAMPED AND WORKSHEETS ATTACHED
 TO EACH SET OF PLANS PRIOR TO RESUBMITT-
 ING FOR REVIEW WITH WPB. 101.4.7
 4) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD. 2938-96. PHONE NUMBER
 (561) 837-4074.
 5) SHT A.71.02 MENS/WOMENS 2ND THRU 5TH
 FLOOR PLAN FOR TOILET ROOMS. SHOW 5'
 TURNING AREA IN TOILET ROOM, NOT IN THE
 STALL.
 6) SHT A.71.02 SHOW TURNING AREA FOR
 TOILET AREA FOR TOILET ROOM WITH ELEVAT-
 ION INDICATORS 7 & 8.
 7) SHT A.71.02 SHOW MEASURMENT FROM CEN-
 TER OF WATER CLOSET TO WALL FOR EACH
 ACCESSIBLE W/C PER FIGURES 30 & 30E. -
 SHOW MEASUREMENT FROM CENTER OF ACCESSI-
 BLE LAVS TO WALL. MIN. 15".104.2.1
 8) SHT P2.1A NO SANT. SHOWN FOR CAFE OR
 TOILET ROOMS FOR BACK. PLEASE CLARIFY
 SECTION 104.2.1
 9) SHT 2.1B NO SANT. SHOWN FOR TOILET
 ROOM IN TICKET BOOTH. PLEASE CLARIFY.
 SECTION 104.2.1
 10) SHT P2.2A SANT; PIPING SHOW BETWEEN
 COLS. X5 & X6 OUTSIDE BLDG FOOTPRINT.
 PLEASE CLARIFY. SECTION 104.2.1
 11) SHT P2.6 ROOF PLAN, INDICATE HOW UP-
 PER ROOFS SHALL BE DRAINED. SHOW CLACUL-
 ATIONS FOR ROOF AREAS BETWEEN COLS. X5
 AND X8. SHOW 1/2 AREA OF ALL VERTICAL
 WALLS AND AREA OF ROOF ABOVE DRAINING ON
 TO ROOF AREAS ADDED TO CALCULATIONS.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 12) SHOW LOCATION OF SECONDARY ROOF
 DRAINS. SHOW PIPING OF SECONDARY ROOF
 DRAINS WITH ALL PIPE SIZES SHOWN. SECT-
 ION 1107.
 13) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BLDG. SECTION 608.
 13.2
 14) SHTS P3.1A, P3.4A, & P3.5A NO WATER
 SHOWN TO TOILET ROOMS. PLEASE CLARIFY
 SECTION 104.2.1
 15) NO STORM PIPING SHOWN TO THE PARKING
 GARAGE. PLEASE CLARIFY.
 16) SHT P5.1 SANITARY ISOMETRIC DIAGRAM
 INDICATE DFU'S AT THE BASE OF EACH STACK
 AND SHOW DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. TABLE 710.1
 17) SHT P5.1 SECTION 903.4 THE VENT
 STACK SHALL CONNECT AT OR BELOW THE LOW-
 EST HORIZONTAL BRANCH.
 18) SHT P5.1 SANT RISER DOES NOT REFLECT
 THE FLOOR PLAN ON SHTS P2.2A, P2.3A,
 P2.4A, & P2.5A. EXTRA FLOOR DRAINS ARE
 ON RISER PAST LAVS IN MENS TOILET ROOM.
 - FLOOR PLAN SHOWS 1 RISER TO LAVS AT
 THE SIDE WALL OF THE LAVS AND PIPES THRU
 THE WALL IN 2" PIPE FOR ALL THREE LAVS.
 ON THE RISER IT SHOWS 2 RISERS, ONE
 PICKS UP 2 LAVS AND THE OTHER RISER
 PICKS UP 1 LAV. PLEASE CLARIFY, CORREL-
 ATE PLANS. SECTION 104.2.1
 19) SHT P6.1 WATER HAMMER ARRESTORS ON
 THE ISOMETRIC DIAGRAM SHALL BE LOCATED
 NEAR THE FIXTURES, NOT IN THE CEILING.
 PDI-WH 201 & MANUF. INSTALL. INSTRUCTION
 20) SUBMIT INFORMATION & RISER DIAGRAM
 FOR BUILDING STORM DRAIN AND RISERS.
 SHOW PIPE SIZE AND SQUARE FOOTAGE AS IT
 ACCUMULATES IN SYSTEM. SHOW TERMINATION
 OF SYSTEM. SECTION 104.2.1
 21) PLANS DO NOT SEEM TO BE COMPLETE.
 MORE COMMENTS MAY FOLLOW ON NEXT REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]