Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-07 00:00:00DENIED:
 ARCHITECTURAL PLANS ARE INCOMPLETE.
 PLEASE INDICATE RATING FOR CORRIDORS.
 DOOR SCHEDULE DOES NOT GIVE FIRE
 RESISTANCE RATING.
  
 1.PLEASE CLARIFY OUTSIDE AIR INTAKE.
 DUCTS THAT PENETRATE MORE THAN 1 FLOOR
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE,
 PER 2001 FBC(M) 607.4. PROVIDE DETAIL
 FOR THE SHAFT ENCLOSURE AND INDICATE
 RATING OF THE ENCLOSURE.
  
 2.PLAN SHEET M2.3, 10" DUCT TO
 VAV-3-6 FIRE DAMPER IS NOT LOCATED AT
 THE WALL.
  
 3.INDICATE CONDENSATE, LINE SIZE,
 MATERIAL, LAYOUT AND TERMINATION PER
 2001 FBC(M) 307.2.1.
  
 4.PLAN SHEET M2.2 & M2.3, INDICATE
 AHU-2, PLANS DO NOT INDICATE AHU-3 AS
 LISTED ON THE EQUIPMENT SCHEDULE.
 PLEASE CLARIFY.
  
 5.PROVIDE CWS/R LINE SIZE ON PLAN
 SHEETS M2.2, M2.3, M2.4 & THROUGH PUMPS
 AND COOLING TOWER.
  
 6.PLAN SHEETS M2.3 & M2.4 M2,M4,M5
 DUCT PENETRATING SHAFT, MISSING FIRE
 DAMPERS.
  
 7.PLANS ARE NOT SIGNED, SEALED OR
 DATED AS REQUIRED PER FS 471.025 & FAC
 61G15-23.002.
  
 8.ENERGY CALCULATIONS ARE REQUIRED PER
 2001 FBC CHAPTER 13 SUB-CHAPTER 4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.