Date |
Text |
2004-06-07 00:00:00 | DENIED: |
| ARCHITECTURAL PLANS ARE INCOMPLETE. |
| PLEASE INDICATE RATING FOR CORRIDORS. |
| DOOR SCHEDULE DOES NOT GIVE FIRE |
| RESISTANCE RATING. |
| |
| 1.PLEASE CLARIFY OUTSIDE AIR INTAKE. |
| DUCTS THAT PENETRATE MORE THAN 1 FLOOR |
| SHALL BE PROTECTED BY A SHAFT ENCLOSURE, |
| PER 2001 FBC(M) 607.4. PROVIDE DETAIL |
| FOR THE SHAFT ENCLOSURE AND INDICATE |
| RATING OF THE ENCLOSURE. |
| |
| 2.PLAN SHEET M2.3, 10" DUCT TO |
| VAV-3-6 FIRE DAMPER IS NOT LOCATED AT |
| THE WALL. |
| |
| 3.INDICATE CONDENSATE, LINE SIZE, |
| MATERIAL, LAYOUT AND TERMINATION PER |
| 2001 FBC(M) 307.2.1. |
| |
| 4.PLAN SHEET M2.2 & M2.3, INDICATE |
| AHU-2, PLANS DO NOT INDICATE AHU-3 AS |
| LISTED ON THE EQUIPMENT SCHEDULE. |
| PLEASE CLARIFY. |
| |
| 5.PROVIDE CWS/R LINE SIZE ON PLAN |
| SHEETS M2.2, M2.3, M2.4 & THROUGH PUMPS |
| AND COOLING TOWER. |
| |
| 6.PLAN SHEETS M2.3 & M2.4 M2,M4,M5 |
| DUCT PENETRATING SHAFT, MISSING FIRE |
| DAMPERS. |
| |
| 7.PLANS ARE NOT SIGNED, SEALED OR |
| DATED AS REQUIRED PER FS 471.025 & FAC |
| 61G15-23.002. |
| |
| 8.ENERGY CALCULATIONS ARE REQUIRED PER |
| 2001 FBC CHAPTER 13 SUB-CHAPTER 4 |
| |