Text |
2004-05-04 00:00:00 | 1) SITE PLAN DOES NOT ILLUSTRATE NEW |
| OR EXISTING FIRE HYDRANTS. |
| |
| 2) DEMOLITION, RENOVATION, AND |
| CONSTRUCTION TO COMPLY WITH |
| NFPA 241. |
| |
| 3) TEMPORARY STANDPIPE SYSTEMS |
| REQUIRED WHEN THE BUILDING REACHES |
| THREE FLOORS OR THIRTY FEET IN HEIGHT. |
| |
| 4) STAIRS ARE TO BE KEPT UP WITH |
| CONSTRUCTION. |
| |
| 5) TACTILE SIGNAGE REQUIRED AT EXITS. |
| |
| 6) ALL SHAFTS THAT ARE LARGE ENOUGH |
| FOR PERSONS TO FALL INTO MUST BE |
| MARKED "SHAFTWAY" WITH 6" LETTERS. |
| |
| 7) BUILDING ADDRESSES REQUIRED. A |
| MINIMUM OF AT LEAST 6" HIGH NUMBERS. |
| |
| 8) KNOX-BOXES WILL BE REQUIRED. |
| |
| 9) LOCKING KNOX-BOX CAPS WILL BE |
| REQUIRED FOR THE FIRE DEPARTMENT |
| CONNECTIONS. |
| |
| 10) ALL NEW STAIRS AND RAMPS ARE |
| REQUIRED TO HAVE HANDRAILS ON BOTH |
| SIDES. |
| |
| 11) BUILDINGS WILL BE LOCATED IN THE |
| CITY FIRE LIMITS. CETRAIN RESTRICTIONS |
| WILL APPLY. PLEASE SEE APPENDIX F, |
| LOCAL AMENDMENTS TO THE FLORIDA |
| BUILDING CODE. |
| |
| 12) IT APPEARS THAT STAIR A-B-1 |
| TERMINATES INTO THE LOADING DOCK. |
| PLEASE EXPLAIN RATIONALE. |
| |
| 13) HOW IS ACCESS PROVIDED INTO THE |
| FIRE PUMP ROOM WHEN THE SECURITY |
| GRILL IS DOWN FOR THE GARAGE AREA. |
| |
| 14) PLEASE INDICATE WHICH ELEVATOR(S) |
| WILL BE STRETCHER ACCESSIBLE. |
| |
| 15) PLEASE PROVIDE A LIFE SAFETY PLAN |
| INDICATING OCCUPANT LOADS, TRAVEL |
| DISTANCES, DEAD-ENDS, ETC. |
| |
| 16) PLEASE DISPLAY ALL TENANT SEPARATION |
| WALLS. |
| |
| 17) PLEASE VERIFY DOOR SWINGS. DOOR 111 |
| APPEARS TO SWING IN THE WRONG DIRECTION. |
| |
| 18) HOW IS EXIT ACCESS ACHIEVED TO |
| DOOR 202. A COLUMN AND A PARKING |
| SPACE IS PRESENT. PLEASE EXPLAIN. |
| |
| 19) SAME CONDITION APPEARS TO EXIST |
| FOR DOOR 301. SAME FOR DOOR 401. |
| |
| 20) PLEASE PROVIDE PRESCRIPTIVE |
| STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| AND GUARDRAILS. |
| |
| 21) TWO DOORS CLOSELY SPACED AT STAIR |
| A-1, LEVEL 3. HOW DO PEOPLE MOVE |
| QUICKLY IS TWO DIRECTIONS IN THIS SMALL |
| AREA. |
| |
| 22) STAIR IDENTIFICATION SIGNS REQUIRED. |
| THESE SIGNS SHALL IDENTIFY STAIR |
| NUMBER, TERMINUS TOP AND BOTTOM, AND |
| FLOOR NUMBER. |
| |
| 23) PLEASE INDICATE INTERIOR FINISH |
| FOR WALL AND CEILINGS. |
| |
| 24) DOES THE CORRIDOR CONNECT TO THE |
| EXISTING UNSPRINKLERED PARKING GARAGE. |
| PLEASE ADVISE. PLEASE SEE FS 553.895 (2) |
| |
| 25) PLEASE IDENTIFY HEIGHT OF |
| CONNECTION BRIDGE. A MINIMUM OF 13 FEET |
| 6 INCHES WILL BE REQUIRED. |
| |
| 26) DOOR SCHEDULES DO NOT IDENTIFY |
| REQUIRED FIRE RATINGS. |
| |
| 27) PLEASE EXPLAIN IF CAFE WILL BE |
| COOKING ANY ITEMS THAT PRODUCE SMOKE |
| OR GREASE LADEN VAPORS. IF SO WHERE |
| WILL THE REQUIRED GREASE HOOD DUCT |
| TERMINATE. |
| |
| 28) LOADING DOCK WILL BE REQUIRED TO |
| BE FIRE SPRINKLER PROTECTED. |
| |
| 29) A TWO HOUR FIRE SEPARATION WILL |
| BE REQUIRED FOR ANY PARKING AREAS AND |
| ADJACENT AREAS. |
| |
| 30) PLEASE DISPLAY ALL FIRE RATED WALLS |
| AND SHAFTS AND THEIR APPROPRIATE |
| HOURLY RATINGS. PLEASE PROVIDE UL |
| NUMBERS. |
| |
| 31) NO EXIT SIGNS AND EMERGENCY LIGHTS |
| SHOWN ON FIRST FLOOR A, PAGE E2.1A. |
| |
| 32) WHERE IS THE SECOND EXIT IDENTIFIED |
| ON FIRST FLOOR B, PAGE E2.1B. ALSO |
| EXIT SIGNS SHOWN IN WITHIN PARKING |
| SPACES. |
| |
| 33) WHERE DOES THE EXIT SIGN FROM THE |
| CORRIDOR TO THE BRIDGE LEAD TO. |
| |
| 34) EXIT SIGN MISSING INFRONT OF EXIT |
| FOURTH FLOOR SECTION A, PAGE E2.4A |
| SAME CONDITION EXISTS ON PAGE E2.5A. |
| |
| 35) EMERGENCY LIGHTING REQUIRED IN |
| FIRE PUMP ROOM. |
| |
| 36) PLEASE INDICATE OCCUPANT LOADS |
| FOR ALL STAIRS. AT LEAST ONE STAIR |
| IS BEING SHARED WITH THE GARAGE. |
| |
| 37) NO FIRE SPRINKLER DRAWINGS |
| PROVIDED WITH PLANS. |
| |
| 38) NEW FIRE ALARM SYSTEM SHALL BE |
| UL LISTED FOR CENTRAL STATION SERVICE. |
| |
| 39) PLEASE PROVIDE CONSTRUCTION TYPE |
| FOR THE BUILDING. |
| |
| 40) PLEASE DISPLAY STANDPIPE SYSTEM |
| LOCATIONS. |
| |
| 41) MORE DETAILS REQUIRED FOR FIRE |
| PUMP. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |