Plan Review Notes
Plan Review Notes For Permit 04042022
Permit Number 04042022
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-04 00:00:001) SITE PLAN DOES NOT ILLUSTRATE NEW
 OR EXISTING FIRE HYDRANTS.
  
 2) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 3) TEMPORARY STANDPIPE SYSTEMS
 REQUIRED WHEN THE BUILDING REACHES
 THREE FLOORS OR THIRTY FEET IN HEIGHT.
  
 4) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 5) TACTILE SIGNAGE REQUIRED AT EXITS.
  
 6) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED "SHAFTWAY" WITH 6" LETTERS.
  
 7) BUILDING ADDRESSES REQUIRED. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS.
  
 8) KNOX-BOXES WILL BE REQUIRED.
  
 9) LOCKING KNOX-BOX CAPS WILL BE
 REQUIRED FOR THE FIRE DEPARTMENT
 CONNECTIONS.
  
 10) ALL NEW STAIRS AND RAMPS ARE
 REQUIRED TO HAVE HANDRAILS ON BOTH
 SIDES.
  
 11) BUILDINGS WILL BE LOCATED IN THE
 CITY FIRE LIMITS. CETRAIN RESTRICTIONS
 WILL APPLY. PLEASE SEE APPENDIX F,
 LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE.
  
 12) IT APPEARS THAT STAIR A-B-1
 TERMINATES INTO THE LOADING DOCK.
 PLEASE EXPLAIN RATIONALE.
  
 13) HOW IS ACCESS PROVIDED INTO THE
 FIRE PUMP ROOM WHEN THE SECURITY
 GRILL IS DOWN FOR THE GARAGE AREA.
  
 14) PLEASE INDICATE WHICH ELEVATOR(S)
 WILL BE STRETCHER ACCESSIBLE.
  
 15) PLEASE PROVIDE A LIFE SAFETY PLAN
 INDICATING OCCUPANT LOADS, TRAVEL
 DISTANCES, DEAD-ENDS, ETC.
  
 16) PLEASE DISPLAY ALL TENANT SEPARATION
 WALLS.
  
 17) PLEASE VERIFY DOOR SWINGS. DOOR 111
 APPEARS TO SWING IN THE WRONG DIRECTION.
  
 18) HOW IS EXIT ACCESS ACHIEVED TO
 DOOR 202. A COLUMN AND A PARKING
 SPACE IS PRESENT. PLEASE EXPLAIN.
  
 19) SAME CONDITION APPEARS TO EXIST
 FOR DOOR 301. SAME FOR DOOR 401.
  
 20) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL HANDRAILS
 AND GUARDRAILS.
  
 21) TWO DOORS CLOSELY SPACED AT STAIR
 A-1, LEVEL 3. HOW DO PEOPLE MOVE
 QUICKLY IS TWO DIRECTIONS IN THIS SMALL
 AREA.
  
 22) STAIR IDENTIFICATION SIGNS REQUIRED.
 THESE SIGNS SHALL IDENTIFY STAIR
 NUMBER, TERMINUS TOP AND BOTTOM, AND
 FLOOR NUMBER.
  
 23) PLEASE INDICATE INTERIOR FINISH
 FOR WALL AND CEILINGS.
  
 24) DOES THE CORRIDOR CONNECT TO THE
 EXISTING UNSPRINKLERED PARKING GARAGE.
 PLEASE ADVISE. PLEASE SEE FS 553.895 (2)
  
 25) PLEASE IDENTIFY HEIGHT OF
 CONNECTION BRIDGE. A MINIMUM OF 13 FEET
 6 INCHES WILL BE REQUIRED.
  
 26) DOOR SCHEDULES DO NOT IDENTIFY
 REQUIRED FIRE RATINGS.
  
 27) PLEASE EXPLAIN IF CAFE WILL BE
 COOKING ANY ITEMS THAT PRODUCE SMOKE
 OR GREASE LADEN VAPORS. IF SO WHERE
 WILL THE REQUIRED GREASE HOOD DUCT
 TERMINATE.
  
 28) LOADING DOCK WILL BE REQUIRED TO
 BE FIRE SPRINKLER PROTECTED.
  
 29) A TWO HOUR FIRE SEPARATION WILL
 BE REQUIRED FOR ANY PARKING AREAS AND
 ADJACENT AREAS.
  
 30) PLEASE DISPLAY ALL FIRE RATED WALLS
 AND SHAFTS AND THEIR APPROPRIATE
 HOURLY RATINGS. PLEASE PROVIDE UL
 NUMBERS.
  
 31) NO EXIT SIGNS AND EMERGENCY LIGHTS
 SHOWN ON FIRST FLOOR A, PAGE E2.1A.
  
 32) WHERE IS THE SECOND EXIT IDENTIFIED
 ON FIRST FLOOR B, PAGE E2.1B. ALSO
 EXIT SIGNS SHOWN IN WITHIN PARKING
 SPACES.
  
 33) WHERE DOES THE EXIT SIGN FROM THE
 CORRIDOR TO THE BRIDGE LEAD TO.
  
 34) EXIT SIGN MISSING INFRONT OF EXIT
 FOURTH FLOOR SECTION A, PAGE E2.4A
 SAME CONDITION EXISTS ON PAGE E2.5A.
  
 35) EMERGENCY LIGHTING REQUIRED IN
 FIRE PUMP ROOM.
  
 36) PLEASE INDICATE OCCUPANT LOADS
 FOR ALL STAIRS. AT LEAST ONE STAIR
 IS BEING SHARED WITH THE GARAGE.
  
 37) NO FIRE SPRINKLER DRAWINGS
 PROVIDED WITH PLANS.
  
 38) NEW FIRE ALARM SYSTEM SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 39) PLEASE PROVIDE CONSTRUCTION TYPE
 FOR THE BUILDING.
  
 40) PLEASE DISPLAY STANDPIPE SYSTEM
 LOCATIONS.
  
 41) MORE DETAILS REQUIRED FOR FIRE
 PUMP.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910