Plan Review Notes For Permit 04042022 |
Permit Number |
04042022 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-13 00:00:00 | | | ELECTRICAL PLANS ARE INCOMPLETE AND DO | | NOT CONTAIN ENOUGH INFORMATION FOR | | REVIEW. | | SUBMIT DRAWINGS PER 2002 NEC. INCLUDE | | LOAD CALCULATIONS, CONDUCTOR AND | | RACEWAY SIZES,PANEL SCHEDULES FOR ALL | | PANELS(ONLY "L" SUBMITTED-TWICE,SEE | | E6.1 & E6.2), THE TRANSFORMER RATINGS | | FOR THE EQUIPMENT BEING USED FOR THE | | SERVICE AND SUB FEEDS,LOCATION OF | | LUMINAIRES AND RECEPTACLES. COMPLETE | | THE LIGHTING FIXTURE SCHEDULE. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|