2004-05-10 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR(S) FROM MAINS TO
 PANELS. 250.24, 250.110, SIZE PER 250.
 122.
  
 2)NOTE: PLEASE HAVE ARCH SIGN WITH
 SIGNATURE CONTAINING A MIN IF FIRST
 AND LAST NAME. FIRST NAME APPEARS TO BE
 INITIALS. PER FS 481.221.
 DBPR HAS MENTIONED INITIALS ARE NOT
 PERMITTED.
  
 3)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 4)NOTE: PLEASE SEE NFPA-72FOR LOCATION
 OF SD IN MASTER BEDROOM. TO BE LOCATED
 W/IN 3' OF POINT OF CEILING.
  
 5)NOTE: PLEASE SEE 210.52C 2, 4
 FOR SEPARATE COUNTERSPACES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  