Plan Review Notes
Plan Review Notes For Permit 04041947
Permit Number 04041947
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-04-29 00:00:00*************DENIED*********************
 1) UNDER SEQUENCE OF OPERATION THE DUCT
 DETECTORS SHALL ACTIVATE GENERAL FIRE
 ALARM SIGNAL NOT A SUPERVISORY AND
 REPORTED TO THE CENTRAL STATION FACILITY
 (PER FIRE MARSHAL OF WEST PALM BEACH).
  
 2) FIRE ALARM CIRCUITS AND DEVICES SHALL
 BE CLASS "A" OR FULLY ADDRESSABLE UNLESS
 EXISTING.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910