Plan Review Notes
Plan Review Notes For Permit 04041895
Permit Number 04041895
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
  
 1) SHT A1.2 A DRINKING FOUNTAIN IS REQ-
 UIRED PER TABLE 403.1. ALSO SEE SECTION
 410.1
 2) SHT A1.2 SINKS SHALL COMPLY WITH SEC.
 11-4.24 AND ALL SUBSECTIONS. SHOW CLEAR
 FLOOR SPACE, HEIGHT, KNEE CLEARANCE, EX-
 POSED PIPES AND SURFACES ECT.
 3) SHT P-1 FLOOR DRAINS ARE NOT APPROVED
 FOR INDIRECT WASTE. SEE SECTIONS 802.3
 AND 802.3.2.
 4) SHT P-1 SUBMIT CALCULATIONS FOR POINT
 LOADING OF BOTTON CHORD OF THE BAR JOIST
 AT WATER HEATER. INDICATE WHERE THE LOAD
 IS BEING TRANSFERRED TO. SECTION 1614.2.
 1.
  
 REVIEW BY KEN STEVENS