Plan Review Notes For Permit 04041895 |
Permit Number |
04041895 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-28 00:00:00 | ********** UNSAT *********** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | AND PANEL SCHEDULES SUBMITTED. | | PANEL 17LA IS SHOWN ON SCHEDULES BUT | | NOT ON RISER? | | PANEL 17L INDICATES 225A MCB ON RISER | | YET BLANKS FOR MLO/MCB ARE SHOWN ON | | SCHEDULE? | | | | 2)NOTE" PLEASE CLARIFY REQ'D EQUIPMENT | | GROUNDING CONDUCTOR TO AND FROM TRANS- | | -FORMER.? 250.30, 250.110 ETC. | | PLEASE ALSO CLARIFY METHOD OF EQUIPMENT | | GRNDS FOR OTHER FEEDS. | | | | 3)NOTE: PLEASE CLARIFY LOCATION OF ALL | | EELECTRICAL EQUIPMENT SHOWN. PANELS? | | TRANSFORMER ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|