2004-05-17 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04041895 |
| ADD: 222 LAKEVIEW AV |
| CONT: HEDRICK BROTHERS |
| TEL: (561)718-8341 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEETSA1.3 INDICATE VARIOUS SOFFITS |
| BUT NO DETAIL AS TO WHAT MATERIAL THEY |
| SOFFITS ARE FASTENED TO NOR THE FASTENER |
| |
| 2) DOOR# 1 DOES NOT INDICATE WHAT THE |
| FIRE RATING IS PROVIDE IF FOR EXISTING |
| DOORS? |
| |
| 3) DOOR #18 & 19 DO NOT PROVIDE WHAT THE |
| FIRE RESISTANCE RATING IS? |
| |
| 4) TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 6) TYPE I/ II BUILDINGS WOOD IN PARTI- |
| TIONS BLOCKING, BACKING MUST BE FIRE |
| RETARDANT TREATED WOOD, 609.1.2. |
| |
| 7) KITHEN ELEVATION, 11-4.24.4 SINK |
| HEIGHT. SINKS SHALL BE MOUNTED WITH THE |
| COUNTER OR RIM NO HIGHER THAN 34INCHES. |
| |
| 8) PROVIDE FIRE SPRINKLER PLANS. |
| |