2004-05-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04041895
 ADD: 222 LAKEVIEW AV
 CONT: HEDRICK BROTHERS
 TEL: (561)718-8341
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEETSA1.3 INDICATE VARIOUS SOFFITS
 BUT NO DETAIL AS TO WHAT MATERIAL THEY
 SOFFITS ARE FASTENED TO NOR THE FASTENER
  
 2) DOOR# 1 DOES NOT INDICATE WHAT THE
 FIRE RATING IS PROVIDE IF FOR EXISTING
 DOORS?
  
 3) DOOR #18 & 19 DO NOT PROVIDE WHAT THE
 FIRE RESISTANCE RATING IS?
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6) TYPE I/ II BUILDINGS WOOD IN PARTI-
 TIONS BLOCKING, BACKING MUST BE FIRE
 RETARDANT TREATED WOOD, 609.1.2.
  
 7) KITHEN ELEVATION, 11-4.24.4 SINK
 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34INCHES.
  
 8) PROVIDE FIRE SPRINKLER PLANS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026