2004-05-21 00:00:00 | BUILDING PLAN REVIEW: FAILED |
| |
| 1. A COPY OF THE RECORDED NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2. THE FLORIDA ENERGY EFFICIENCY CODE |
| FORM STATES THE EXTERIOR CONCRETE WALLS |
| |
| HAVE AAN R-4.2 RATING.THE PLANS STATE |
| R12.9.PLEASE CLARIFY. |
| |
| 3. VERIFY THAT ALL USP & SIMPSON |
| CONNECTORS ARE INSTALLED ACCORDING TO |
| MANUFACTURERS SPECS. REVISE ON PAGE |
| RF-1. |
| |
| 4. ROYAL WALL: SUBMIT A LETTER FROM A |
| LICENSED THRESHOLD INSPECTOR STATING |
| THAT AN INSPECTION WILL BE MADE AT THE |
| MANUFACTURED SITE OF THE JOB SPECIFIC |
| COMPONENTS TO VERIFY CONSTRUCTION |
| COMPLIANCE OF THE COMPONENTS WITH THE |
| ENGINEERED DESIGN. |
| |
| 5. THE PLANS SPECIFY AN IMACT S/H |
| WINDOW IN THE DEN.IS IT A 701 IMPACT? |
| IF SO YOU HAVE THE FLORIDA PRODUCT |
| APPROVALS FOR IT. |
| |
| 6. STATE STATUTE REQUIRED ARCHITECTS & |
| ENGINEERS TO USE FULL SIGNATURES ON |
| PLANS & ENGINEERING.INITIALS ARE NOT |
| ACCEPTABLE.THEY HAVE TO BE ORIGINAL |
| NOT PHOTO COPIES. |
| |
| 7. ACCORDING TO SBCCI BUILDING |
| VALUATIONTABLE THE VALUE FOR THE A/C |
| SPACE IS $76.96.THE UNCONDITIONED |
| SPACE REMAINS $41.60.THE NEW ADJUSTED |
| FEE REMAINING TO BE PAID BEFORE |
| PERMITTING IS $60.75. |
| |
| 8. SUBMIT THE FLORIDA PRODUCT APPROVALS |
| FOR THE WEATHERGUARD STORM PANELS. |
| |