2004-05-21 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2. THE FLORIDA ENERGY EFFICIENCY CODE
 FORM STATES THE EXTERIOR CONCRETE WALLS
  
 HAVE AAN R-4.2 RATING.THE PLANS STATE
 R12.9.PLEASE CLARIFY.
  
 3. VERIFY THAT ALL USP & SIMPSON
 CONNECTORS ARE INSTALLED ACCORDING TO
 MANUFACTURERS SPECS. REVISE ON PAGE
 RF-1.
  
 4. ROYAL WALL: SUBMIT A LETTER FROM A
 LICENSED THRESHOLD INSPECTOR STATING
 THAT AN INSPECTION WILL BE MADE AT THE
 MANUFACTURED SITE OF THE JOB SPECIFIC
 COMPONENTS TO VERIFY CONSTRUCTION
 COMPLIANCE OF THE COMPONENTS WITH THE
 ENGINEERED DESIGN.
  
 5. THE PLANS SPECIFY AN IMACT S/H
 WINDOW IN THE DEN.IS IT A 701 IMPACT?
 IF SO YOU HAVE THE FLORIDA PRODUCT
 APPROVALS FOR IT.
  
 6. STATE STATUTE REQUIRED ARCHITECTS &
 ENGINEERS TO USE FULL SIGNATURES ON
 PLANS & ENGINEERING.INITIALS ARE NOT
 ACCEPTABLE.THEY HAVE TO BE ORIGINAL
 NOT PHOTO COPIES.
  
 7. ACCORDING TO SBCCI BUILDING
 VALUATIONTABLE THE VALUE FOR THE A/C
 SPACE IS $76.96.THE UNCONDITIONED
 SPACE REMAINS $41.60.THE NEW ADJUSTED
 FEE REMAINING TO BE PAID BEFORE
 PERMITTING IS $60.75.
  
 8. SUBMIT THE FLORIDA PRODUCT APPROVALS
 FOR THE WEATHERGUARD STORM PANELS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713