Plan Review Notes For Permit 04041827 |
Permit Number |
04041827 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-11 00:00:00 | DENIED: | | RETURN AIR FROM BEDROOM AREAS ARE NOT | | SIZED PROPERLY.PER THE REVISED 2001 | | FBC(M) 601.4 EFFECTIVE JUNE 30, 2003, | | THE RETURN AIR SHALL BE SIZED AS | | FOLLOWS: | | | | BR SUITE #2 RETURN AIR JUMPER = 13" MIN | | BR SUITE #3 RETURN AIR = 10" | | MASTER SUITE RETURN AIR = 15" | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|