2004-05-21 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERK OFFICE AND A
 COPY SUBMITTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 2. VERIFY TYPE OF WINDOW BEING
 INSTALLED IN THE DEN (S/H IMPACT).
  
 3. THE FLORIDA ENERGY EFFICIENCY CODE
 STATES THE EXTERIOR CEMENT WALLS ARE
 R-4.2 BUT THE PLANS SHOW R-12.9. PLEASE
 CLARIFY.
  
 4.VERIFY ALL USP & SIMPSON CONNECTORS
 ARE INSTALLED ACCORDING TO
 MANUFACTURERS SPECS. REVISE ON RF-1
  
 5. THE STATE PRODUCT APPROVAL IS MISSING
 FOR THE GOLF CART GARAGE DOOR.
  
 6. ROYAL WALL: SUBMIT A LETTER FROM A
 LICENSED THRESHOLD INSPECTOR STATING
 THAT AN INSPECTION WILL BE MADE AT THE
 MANUFACTURED SITE OF THE JOB SPECIFIC
 COMPONENTS TO VERIFY COMPLIANCE OF THE
 COMPONENTS WITH THE ENGINEERED DESIGN.
  
 7. STATE STATUTES REQUIRES ORIGINAL
 FULLSIGNATURES BY THE ARCHITECT AND
 ENGINEERON ALL PLANS & REPORTS.NO
 INITIALS AREPERMITTED. ALL SIGNATURES
 HAVE TO BE
 ORIGINAL, NOT PHOTO COPIES.
  
 8. THE FLORIDA PRODUCT APPROVAL FOR THE
 WEATHERGUARD STORM PANELS IS MISSING.
 PLEASE SUBMIT.
  
 9. ACCORDING TO SBCCI VALUATION TABLE
 THE A/C AREA IS BASED ON $76.96 PER SQ
 FT.THE UNCONDITIONED SPACE REMAINS AT
 $41.60.THE ADDITIONAL FEES AMOUNTS TO
 $65.09.
  
 10 THE SQ. FT. ON PLANS DOES NOT AGREE
 WITH APPLICATION.PLEASE CORRECT.
 SHOULD BE 4015 PER PLANS.
  