2004-05-21 00:00:00 | BUILDING PLAN REVIEW: FAILED |
| |
| 1. A NOTICE OF COMMENCEMENT MUST BE |
| FILED AT THE COUNTY CLERK OFFICE AND A |
| COPY SUBMITTED BEFORE A PERMIT CAN BE |
| ISSUED. |
| |
| 2. VERIFY TYPE OF WINDOW BEING |
| INSTALLED IN THE DEN (S/H IMPACT). |
| |
| 3. THE FLORIDA ENERGY EFFICIENCY CODE |
| STATES THE EXTERIOR CEMENT WALLS ARE |
| R-4.2 BUT THE PLANS SHOW R-12.9. PLEASE |
| CLARIFY. |
| |
| 4.VERIFY ALL USP & SIMPSON CONNECTORS |
| ARE INSTALLED ACCORDING TO |
| MANUFACTURERS SPECS. REVISE ON RF-1 |
| |
| 5. THE STATE PRODUCT APPROVAL IS MISSING |
| FOR THE GOLF CART GARAGE DOOR. |
| |
| 6. ROYAL WALL: SUBMIT A LETTER FROM A |
| LICENSED THRESHOLD INSPECTOR STATING |
| THAT AN INSPECTION WILL BE MADE AT THE |
| MANUFACTURED SITE OF THE JOB SPECIFIC |
| COMPONENTS TO VERIFY COMPLIANCE OF THE |
| COMPONENTS WITH THE ENGINEERED DESIGN. |
| |
| 7. STATE STATUTES REQUIRES ORIGINAL |
| FULLSIGNATURES BY THE ARCHITECT AND |
| ENGINEERON ALL PLANS & REPORTS.NO |
| INITIALS AREPERMITTED. ALL SIGNATURES |
| HAVE TO BE |
| ORIGINAL, NOT PHOTO COPIES. |
| |
| 8. THE FLORIDA PRODUCT APPROVAL FOR THE |
| WEATHERGUARD STORM PANELS IS MISSING. |
| PLEASE SUBMIT. |
| |
| 9. ACCORDING TO SBCCI VALUATION TABLE |
| THE A/C AREA IS BASED ON $76.96 PER SQ |
| FT.THE UNCONDITIONED SPACE REMAINS AT |
| $41.60.THE ADDITIONAL FEES AMOUNTS TO |
| $65.09. |
| |
| 10 THE SQ. FT. ON PLANS DOES NOT AGREE |
| WITH APPLICATION.PLEASE CORRECT. |
| SHOULD BE 4015 PER PLANS. |
| |