Plan Review Notes
Plan Review Notes For Permit 04041818
Permit Number 04041818
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-10 00:00:00************** UNSAT **********
  
 1)NOTE HAVE ARCH SIGN FULL SIGNATURE PER
 FS 481.221/ FAC 61G1-16
 PER DBPR/FBPE'S INITIALS ARE NOT PERMIT-
 -TED. MIN OF FIRST AND LAST NAME MUST BE
 SIGNED.
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 THIS MAY BE A PROVISO BEFORE ROUGH DUE
 TO UNKNOWN # OF FIXTURES AT THIS TIME.
  
 3)NOTE: PLEASE MOVE SD INTO MASTER BED
 RM. PLEASE VERFIY OTHER RM?
 THIS MAY ALSO BE REDLINED/ PROVISO.
  
 NOTE # 1 MUST BE ADDRESSED AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]