2004-05-10 00:00:00******* UNSAT ************
  
 1)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND. THIS CAN BE A PROVISO BEFORE
 ROUGH, DUE TO THE UNKNOWN # OF FIXTURES
 AT THIS TIME.
  
 2)NOTE: PLEASE HAVE ARCH SIGN WITH
 SIGNATURE. FS 481.221/FAC 61G1-16
  
 3)NOTE: PLEASE SEE SD NEEDS TO BE MOVED
 INTO MASTER BEDRM. SEEMS TO HAVE ANOTHER
 SD MISSING IN OTHER RM? RM DESIGNATION
 NO ON PLANS AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  