2004-05-21 00:00:00 | BUILDING PLAN REVIEW; FAILED |
| |
| |
| 1. A COPY OF THE RECORDED NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2. THE FLORIDA ENERGY EFFICIENCY CODE |
| FORM STATES THE EXTERIOR CONCRETE WALLS |
| HAVE AN R-4.2.PLANS STATE R-12.9. |
| PLEASECLARIFY. |
| |
| 3.VERIFY THAT ALL USP AND SIMPSON |
| CONNECTORS ARE INSTALLED ACCORDING TO |
| MANUFACTURERS SPECS. REVISE ON PAGE |
| RF-1. |
| |
| 4.ROYAL WALL: SUBMIT A LETTER FROM A |
| LICENSED THRESHOLD INSPECTOR STATING |
| THAT AN INSPECTION WILL BE MADE AT THE |
| MANUFACTURED SITE OF THE JOB SPECIFIC |
| COMPONENTS TO VERIFY CONSTRUCTION |
| COMPLIANCE OF THE COMPONENTS WITH THE |
| ENGINEERED DESIGN. |
| |
| 5. ACCORDING TO SBCCI BUILDING |
| VALUATION TABLE THE VALUATION FOR A/C |
| SPACE IS @ $76.96. THE UNCONDITIONED |
| SPACE REMAINS @ $41.60. THE ADJUSTED |
| FEES DUE FOR THIS HOUSE IS $60.75 |
| BEFOREA PERMIT CAN BE ISSUED. |
| |
| 6. PROVIDE FLORIDA PRODUCT APPROVAL FOR |
| THE WEATHERGUARD STORM PANELS. |
| |
| 7. CLARIFY THE MODEL OF THE IMPACT |
| WINDOW IN THE DEN.IS IT A MODEL SH701 |
| IMPACT? IF SO YOU HAVE THE FLORIDA |
| PRODUCT APPROVALS SUBMITTED FOR IT. |
| |
| 8ACCORDING TO STATE STATUTE ALL ENGINEER |
| AND ARCHITECTS MUST SIGN WITH FULL |
| SIGNATURE ALL PLANS & ENGINEERING |
| REPORTS. |
| |