Plan Review Notes For Permit 04041799
Permit Number 04041799
Review Stop P
Sequence Number 1
Notes
Date Text
2004-05-12 00:00:00PLU,BING PLAN REVIEW,DENIED FBC 2001
 1) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 2 ) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
 (3) SEC 424.2.12.1 PRESSURE TEST.
 NO AIR TEST WILL BE APPROVED FOR PVC
 PIPE.
 (4) SEC 424.2.13.2 JOINTS, CONNECTIONS.
 PURPLE PRIMER, REQUIRED ON PVC PIPING.
 (5) SEC 104.6.5 BUILDING PERMIT VALUE.
 VALUATION BASED ON TOTAL REPLACEMENT
 VALUE.TO INCLUDE STRUCTAL, ELECTRICAL
 PLUMBING, MECHANICAL,INTERIOR FINISH,
 NORMAL SITE WORK,ARCHITECTURAL & DESIGN
 FEES, EXCLUDING ONLY LAND VALUE.
 (6) FPC 2001 SEC 310.3 CONNECTION TO
 THE DRAINAGE SYSTEM.SHT 1 VAC PCAK
 WASTE TO SANITARY SEWER.
 END OF COMMENTS QUESTIONS 561-805-6692