Plan Review Notes For Permit 04041783 |
Permit Number |
04041783 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-05-03 00:00:00 | ******** REDLINED / PROVSIO ********** | | | | REVISE PLANS BEFORE ROUGH. | | | | 1)NOTE: PLEASE SEE RANGE LOAD TO BE FIG | | AT 8KW MIN PER 220.19/ SHOWN AT 7.5KW | | | | 2)NOTE: PLEASE SEE MAX LOAD ON A 1P-20A | | CIRCUIT IS 1.9KW 80%. IRRG PUMP, WASHER | | SHOWN AT 2KW | | | | SD'S ARE TO BE INSATELLED PER NFPA-72 | | 8-1.4.2 | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|