Plan Review Notes
Plan Review Notes For Permit 04041783
Permit Number 04041783
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-03 00:00:00******** REDLINED / PROVSIO **********
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: PLEASE SEE RANGE LOAD TO BE FIG
 AT 8KW MIN PER 220.19/ SHOWN AT 7.5KW
  
 2)NOTE: PLEASE SEE MAX LOAD ON A 1P-20A
 CIRCUIT IS 1.9KW 80%. IRRG PUMP, WASHER
 SHOWN AT 2KW
  
 SD'S ARE TO BE INSATELLED PER NFPA-72
 8-1.4.2
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  