Plan Review Notes
Plan Review Notes For Permit 04041742
Permit Number 04041742
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-06 00:00:00******** REDLINED/ PROVSIO *********
  
 1)NOTE : LOAD FOR RANGE TO BE A MIN OF
 8KW PER 220.19
  
 2)NOTE: MAX LOAD FOR A 1P20A CIRCUIT IS
 1.9KW. IRRG PUMP, WASHER SHOWN AT 2KW.
  
 SD'S TO BE INSTALLED PER NFPA-72 8-1.4.2
  
  
 REVISE PLANS BEFORE ROUGH.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717