Plan Review Notes
Plan Review Notes For Permit 04041733
Permit Number 04041733
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-04 00:00:00******** REDLINED /PROVISO *******
  
 REVISE PLANS BEFORE ROUGH.
  
 1)NOTE: LOAD CALCUALTIONS TO REFLECT
 A MIN OF 8KW FOR RANGE PER 220.19
  
 2)NOTE IRRG PUMP, WASHER SHOWN EXCEEDING
 MAX LOAD OF 1.9KW ON A 1-P20A CIRCUIT.
  
 SD'S NOTED TO BE INSTALLED PER NFPA-72
 8-1.4.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW